Max. Refrigerant Piping Length; Max. Height Difference; Additional Refrigerant Charge - Mitsubishi Electric MUZ-AP25VG - E1 Service Manual

Outdoor unit, split-type air conditioners
Table of Contents

Advertisement

MUZ-AP50VG
MUZ-AP50VGH
Refrigerant pipe ø 9.52
(with heat insulator)
Flared connection
Flared connection
Refrigerant pipe ø 6.35
(with heat insulator)
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
MUZ-AP25/35/42/50VG(H)
ADDITIONAL REFRIGERANT CHARGE (R32: g)
Outdoor unit
Model
precharged
MUZ-AP25VG(H)
MUZ-AP35VG(H)
MUZ-AP42VG(H)
MUZ-AP50VG(H)
1,000
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7)
NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
OBH789
Muffler
4-way valve
Muffler
Stop valve
(with service port)
Discharge
temperature
thermistor
RT62
Compressor
Stop valve
Capillary tube
(With strainer)
ø4.0×ø2.4×240
Refrigerant piping: m
Max. Length A
20
Indoor
unit
Max. Height
difference
B
Max. Length
7 m
8 m
550
0
20
700
Outdoor heat
exchanger
temperature
thermistor
RT68
Defrost
thermistor
RT61
Capillary tube
ø3.0×ø2.0×210(×2)
LEV
Strainer
#100
Max. Height difference B
12
A
Outdoor unit
Refrigerant piping length (one way)
9 m
10 m
11 m
12 m
40
60
80
14
Outdoor
heat
Ambient
exchanger
temperature
thermistor
RT65
R.V. coil
heating ON
cooling OFF
Refrigerant flow in cooling
Refrigerant flow in heating
Piping size O.D: mm
Gas
9.52
13 m
14 m
15 m
100
120
140
160
Unit: mm
Liquid
6.35
20 m
260

Hide quick links: