Switches 9 And 10 - Rs232/Rs485 Select; Factory Settings - Baldor MDH1A05TB-RC23 Installation Manual

Mintdrive ii series; mdh1a series; mdh2a series; mdh4a series
Table of Contents

Advertisement

3.9.6 Switches 9 and 10 - RS232/RS485 select

Switch 9 is reserved for Baldor keypad selection.
Switch 10 selects RS232 communications (Off) or RS485/RS422 (On) the next time the
II
MintDrive
is power-cycled.

3.9.7 Factory settings

If switches 1-4 are all in the On position and switch 8 is set to Off, the MintDrive
its preset factory settings at power on (or whenever the processor is reset by WorkBench v5).
CAUTION: Use this function carefully - it will erase your drive setup information.
When using the SW1 DIP switches to reset the MintDrive
parameters including the node number and serial communications baud rate will be reset. In
WorkBench v5, this means it will be necessary to rescan for the MintDrive
project) to enable communication. It will also be necessary to re-tune your motor and drive.
1.
Remove
power.
Figure 22 - Resetting the MintDrive
The Mint keyword FACTORYDEFAULTS can also be used to reset the MintDrive
defaults. However, it will not reset the node number or serial communications baud rate. See
the Mint help file for details.
MN1901
2.
1
On
On
2
3
On
4
On
8
Off
II
to its factory defaults, all
3.
Reapply
power.
II
to its factory default settings
Basic Installation 3-35
www.baldormotion.com
II
will be reset to
II
(by starting a new
II
4.
MintDrive
will
be reset to its
preset factory
settings.
II
to its factory

Advertisement

Table of Contents
loading

Table of Contents