Appendix C Specifications - Siemens SCOR Installation, Operation & Maintenance Instructions Manual

Overcurrent protective relay
Table of Contents

Advertisement

Appendix C Specifications

relay is available in single-phase, three-phase, two­
SCOR
The
phase-with-ground, and three-phase-with-ground configura­
tions, and with the features and c a p a b ilities descri b e d in
Table C.1 .
Current Sensing Inputs
Current Sensing Burden
Frequency (nominal)
Time Overcurrent
Pickup Ranges:
Pickup Adjustment:
Pickup Setting Accuracy:
Pickup Repeatability:
Droput Ratio:
Instantaneous Overcurrent :
Pickup Range:
Pickup Setting Accuracy:
Dropout Ratio:
Table C.1
Specifications
The unit is designed to operate from the secondary of a standard current transformer
rated at 5 A. The maximum continuous current rating for each input is five times tap or
20 A, whichever is less.
The one-second current rating for each input is 50 times tap or 500 A , whichever is
less. Ratings at less than one second are calculated as:
{Klf
where
=
(500
K
A or
=
T
Time that current flows (in seconds)
=
Less than 0.025 ohms per phase at nominal 60 Hz. (see
60 Hz.
Two ranges are available: HIGH (2.0 - 1 1.0 A}, and LOW (0.5 - 5.0 A). Range is
independently specified for phase and ground by the second digit of the Style
Number. The TAP range windows on the front panel indicate which range (HIGH or
LOW} is specified. Selection of the desired tap is made using the rotary selector
switch(s) on the front panel. Refer to the table on the front panel for the various tap
ratings in secondary amps.
Incrementally adjustable over the selected range by a front-panel (TAP) selector switch
("coarse"), and by numerical data entered into the Tap Cal register ("fine").
The accuracy of the pickup setting is +1- 2% of the programmed setting over the full
specified range of the relay at 60 Hz.
Within 2%.
Better than 80% of the established pickup level within 50 milliseconds.
0.5 to 20 times the value of the time overcurrent pickup setting.
The accuracy of the instantaneous pickup setting is
over the full specified range of the relay at 60 Hz.
Better than 80% of the extablished pickup level within 50 milliseconds.
50
times TAPt
Table
+/-
2% of the programmed setting
Page 4 1