Motor Potentiometer (Mop); Fixed Frequency (Ff) - Siemens MICROMASTER 420 Operating Manual

0.12 kw - 11 kw
Hide thumbs Also See for MICROMASTER 420:
Table of Contents

Advertisement

Issue 04/04
6.2.8

Motor potentiometer (MOP)

Setpoint memory of the MOP
P1031 =...
Saves last motor potentiometer setpoint (MOP) that was active before OFF command or
power down.
0
MOP setpoint will not be stored
1
MOP setpoint will be stored (P1040 is updated)
Inhibit negative MOP setpoints
P1032 =...
0
Neg. MOP setpoint is allowed
1
Neg. MOP setpoint inhibited
Setpoint of the MOP
P1040 =...
Determines setpoint for motor potentiometer control.
MOP ramp-up and ramp-down times are defined by the parameters P1120 and P1121.
Possible parameter settings for the selection of MOP:
DIN
BOP
USS on
BOP link
USS on
COM link
CB
6.2.9

Fixed frequency (FF)

Fixed frequency 1
P1001 =...
Can be directly selected via DIN1
(P0701 = 15 16)
Fixed frequency 2
P1002 =...
Can be directly selected via DIN2
(P0702 = 15, 16)
Fixed frequency 3
P1003 =...
Can be directly selected via DIN3
(P0703 = 15, 16)
Fixed frequency 4
P1004 =...
Fixed frequency 5
P1005 =...
Fixed frequency 6
P1006 =...
Fixed frequency 7
P1007 =...
Fixed frequency code –
P1016 =...
Bit 0
Defines the selection method for fixed
frequencies.
Fixed frequency code –
P1017 =...
Bit 1
Fixed frequency code –
P1018 =...
Bit 2
MICROMASTER 420
Compact Operating Manual
Selection
P0719 = 0, P0700 = 2, P1000 = 1
or
P0719 = 1, P0700 = 2
P0719 = 0, P0700 = 1, P1000 = 1
or
P0719 = 11
P0719 = 0, P0700 = 4, P1000 = 1
or
P0719 = 41
P0719 = 0, P0700 = 5, P1000 = 1
or
P0719 = 51
P0719 = 0, P0700 = 6, P1000 = 1
or
P0719 = 61
0.00 Hz
When defining the function of the digital inputs
(P0701 to P0703), three different types can be
selected for fixed frequencies:
15 = Direct selection (binary-coded)
5.00 Hz
10.00 Hz
15.00 Hz
16 = Direct selection + ON command
20.00 Hz
25.00 Hz
17 = Binary coded selection + ON command
30.00 Hz
1
1
2
3
NOTE
For settings 2 and 3, all parameters P1016 to
1
P1019 must be set to the selected value so that
the drive inverter accepts the ON command.
1
MOP up
MOP down
P0702 = 13
P0703 = 14
(DIN2)
UP button
DOWN button
USS control word
USS control word
r2032 Bit13
r2032 Bit14
USS control word
USS control word
r2036 Bit13
r2036 Bit14
CB control word
CB control word
r2090 Bit13
r2090 Bit14
In this particular mode, the appropriate
digital input always selects the associated
fixed frequency, e.g.:
Digital input 3 = selects fixed frequency 3.
If several inputs are simultaneously active,
then these are summed. An ON command is
additionally required.
(binary-coded + On / Off1)
In this mode, the fixed frequencies are
selected as for 15, however these are
combined with an ON command.
(BCD-coded + On/ Off1)
The BCD-coded operating mode is effective
for digital inputs 1 to 3.
Direct selection
Direct selection + ON command
Binary coded selection + ON command
6 Commissioning
0
1
5.00 Hz
(DIN3)
19