ABB 07CR41 Operating Manual page 20

Series 40 and 50
Table of Contents

Advertisement

3
Technical specifications
Creepage distances and clearances
Insulation test
Electromagnetic compatibility
Immunity tests against:
- electrostatic discharge
- radiated fields
- fast transient bursts
- high energy pulse
- conducted high frequencies
Voltage drops and brief power cut-offs
- d.c. power supply
- a.c. power supply
Dielectric tests
Mountings
- DIN rail
- Screw fittings
Connections
- Connectors
- Cross-section for:
earth
inputs
outputs
power supply
bus
- Screw-tightening torque
Serial interface
- for programming
- for the bus
IEC 664 and DIN VDE 0160
IEC 1131-2
IEC 1000-4-2 (level 3)
IEC 1000-4-3 (level 3)
IEC 1000-4-4 (level 3)
IEC 1000-4-5
IEC 1000-4-6 (level 3)
Duration of the power cut-offs: ≤ 10 ms
Time between 2 voltage drops: ≥ 1 s
Duration of the power cut-offs: ≤ 20 ms
Time between 2 voltage drops: ≥ 1 s
IEC 1131-2
35 mm
4 mm diameter screws (M4)
Removable terminal blocks (2.5 mm²)
Rigid or multi-conductor wire AWG 14
(1.95 mm²)
Rigid or multi-conductor wire AWG 18
(0.96 mm²) to AWG 14 (1.95 mm²)
Rigid or multi-conductor wire AWG 14
(1.95 mm²)
Rigid or multi-conductor wire AWG 14
(1.95 mm²)
Twisted pair AWG 24 (0.22 mm²) to AWG
18 (0.8 mm²)
0.8 Nm (given as an indication only)
RS-232/RS-485
RS-485
3 – 2
Advant Controller AC 31 / Issued: 01.99