Samsung AQ12AAMC Service Manual page 11

Indoor/outdoor units
Table of Contents

Advertisement

3-2-3 When the Outdoor Unit Does Not Operate. (Initial Diagnosis)
1)
Checklist :
(1) Is input voltage normal?
(2) Is the set temperature of the remote control higher than room temperature in COOL mode?
(3) Is the POWER IN connector (CN71) linked correctly?
(4) Is the outdoor unit properly connected with the TERMINAL BLOCK connector((N1), 1)?
2)
Troubleshooting procedure
After unplugging out the power cord should be
reconnected within five seconds.
Does the STD lamp blink
Does the timer lamp blink during operation ?
Is the power relay RY71 operated by adjusting the room
Test rod location
+
IC4 Pin No.33
GND
Is rating voltage ±10% range applied relay between Terminal block
10
YES
NO
#
temperature?
Normal
Voltage
-
Condition
RY71 ON
DC 4.8V
NO
NO(N1) and No. 1
YES
Is the room sensor normal register?
10°C
17.96kΩ
NO
!
YES
NO
Power relay is
out of order
!
NO
YES
@
20°C
30°C
12.09kΩ
8.3kΩ
YES
#
Check as in the procedure "No Power parts"
Refer to page 8.
Room temperature sensor is
out of order
@
PCB should be checked.
Microcomputer is
out of order.
PCB should be
checked.
Power relay should be
replaced.
Outdoor unit is
out of order.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uq12aamcAq12aabmcUq12aabmc

Table of Contents