CONDENSATE DRAIN

The condensate drain hose is routed down from the
evaporator drain pan on the right side of the unit
into the compressor compartment. There are three
locations that the drain can exit the cabinet. For a
stand pipe type of drain, the drain hose can exit the
rear of the cabinet. There is adequate hose length to
reach the floor on the right hand side of the unit.
If the drain is to be hard plumbed, there is a 3/4" pipe
connection located on the right hand cabinet side near
the rear and one on the cabinet rear panel. In these
installations the drain tube is to be slipped over the
pipe connection inside of the cabinet.
FIGURE 9A
Side Drain (Side View)
Q-TEC UNIT
FIGURE 9B
Optional Rear Drain
Manual 2100-416J
Page
12 of 27
See Figures 9A, 9B and 9C.
NOTE: Whichever type of drain connection is used a
"P" trap must be formed.
The side drain requires a water trap for proper drainage
(see Figure 9A). The drain can be routed through the floor
or through the wall. If the drain is to be routed through an
unconditioned space, it must be protected from freezing.
The drain line must be able to be removed from the unit
if it is necessary to remove the unit from the wall.
Rear Drain (Top View)
SLEEVE
WATER
TRAP
FIGURE 9C
DRAIN LINE
WALL
(MAXIMUM
10" FOR REAR
DRAIN)
COUPLINGS NOT
SHOWN BUT
RECOMMENDED
FOR EASE OF
REMOVABILITY FOR
SERVICE
WALL BRACKET
UNIT