10

TROUBLESHOOTING

HOW TO CHECK THE PARTS
PLA-P1.6KA.UK, PLA-P2KA.UK, PLA-P2.5KA.UK
PLA-P1.6KA
.UK, PLA-P2KA
1
Parts name
Room temperature
Disconnect the connector then measure the resistance using a tester.
thermistor
(TH1)
(Surrounding temperature 10:~30:)
Pipe temperature
thermistor
(TH2)
Condenser/evaporator
temperature thermistor
(TH5)
Vane motor
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:)
Fan motor
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:)
Relay connector
1
Red
1
White
2
2
3
Black
3
Protector
OFF:130i 5:
ON :80i 20:
Drain pump
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:)
Red
1
2
Red
Drain sensor
Measure the resistance between the terminals using a tester.
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(Surrounding temperature 0:~60:)
1
2
3
.UK, PLA-P2.5KA
1
Normal
4.3k"~9.6k"
Open or short
Normal
15k"
Open or short
Motor terminal
or
Relay connector
Red-Black
White-Black
Normal
290"
Open or short
Normal
0.6k"~6.0k"
Open or short
.UK
1
Check points
Abnormal
(Refer to the thermistor)
Abnormal
Normal
PLA-P
1.6/2/2.5KA.UK
87.2"
104.1"
Abnormal
Abnormal
(Refer to the thermistor)
47
Abnormal
Open or short