87%-Efficiency Boilers –
Special Instructions
NOTE: The constructions of the 84%- (standard)
and 87%-efficiency (optional) boilers are very similar,
and they are installed to the same requirements,
except as noted in this section.

Water Piping

An 87%-efficiency boiler requires a minimum inlet
water temperature of 120ºF (49ºC) to prevent exces-
sive condensation in the combustion chamber. An
87%-efficiency boiler operated with an inlet tempera-
ture of less than 120ºF (49ºC) must have a manual
bypass or an approved low-temperature operation
system to prevent problems with condensation. A man-
ual bypass, shown in Fig. 15, must be piped into the
system at the time of installation. This piping is like a
primary/secondary boiler installation with a bypass in
the secondary boiler piping. Raypak strongly recomm-
10°F T
Model
No.
gpm
302AE
52
402AE
69
502AE
87
652AE
N/A
N/A
752AE
N/A
N/A
902AE
N/A
N/A
Note: Basis for minimum flow is 20 gpm or 40°F ΔT. Basis for maximum flow is 90 gpm.
Combustion
Air Supply
From Inside Building
(Non-Direct Venting)
From Outside Building
(Direct Venting)
Table Q: Category Determination for Venting Purpose and Venting Arrangement
20°F T
P (ft)
gpm
P (ft)
3.3
26
<1.0
6.0
35
1.5
9.7
44
2.5
57
4.4
65
6.1
78
8.9
Table P: Heater Rate of Flow and Pressure Drop
Exhaust
Configuration
Vertical Natural Draft
Venting
Horizontal Through-
the-Wall Venting
Vertical Natural Draft
Venting
Horizontal Through-
the-Wall Venting
ends that a thermometer be placed into the boiler inlet
piping next to the in/out header to facilitate tempera-
ture adjustment. Inlet water temperatures below 120ºF
(49ºC) can excessively cool the products of combus-
tion, resulting in condensation on the heat exchanger.
Venting
CAUTION: Proper installation of flue venting is criti-
cal for the safe and efficient operation of the boiler.
Appliance Categories
See Table Q for appliance category requirements for
the 87%-efficiency Hi Delta.
NOTE: For additional information on appliance cat-
egorization, see appropriate code NFGC (U.S.) and
B149.1 (Canada), or applicable local building codes.
30°F T
Min. Flow
gpm
P (ft)
gpm
N/A
N/A
20
23
<1.0
20
29
1.1
22
38
2.0
28
44
2.8
33
52
4.1
39
Heater Venting
Category
Stainless Steel
II
IV
Stainless Steel
II
IV
39
Max Flow
P (ft)
T gpm
<1.0
26
90
<1.0
35
90
<1.0
40
90
1.1
40
90
1.6
40
90
2.3
40
90
Certified
Combustion Air
Materials
Inlet Material
(Gas Tight)
AL29-4C
Galvanized Steel
(Gas Tight)
PVC
ABS
AL29-4C
CPVC
P (ft)
T
9.8
6
10.0
8
10.4
10
10.8
13
11.3
15
11.7
17