Equipment Combinations; Tx-I/O, Knx Pl-Link; Dali - Siemens PXC3.E16A100A Datasheet

Pxc3.e series; room automation stations
Table of Contents

Advertisement

Communications

Equipment combinations

TX-I/O, KNX PL-Link

DALI

Siemens
Building Technologies
• The room automation stations have a 2-port Ethernet switch to support for low-
cost cabling via line topology.
• A USB Device port is available for service and commissioning.
• TX-I/O modules connected directly to the PXC3 allow for direct connection of
field devices. This offers maximum flexibility.
• The KNX PL-Link peripheral bus supports room operator units, sensors, and
actuating devices. Selected Siemens field devices to the KNX PL-Link bus
(devices with the KNX PL-Link logo) can be connected.
The KNX PL-Link bus supports integration of commercially available devices
with KNX S-Mode (requires ETS engineering).
• The DALI bus supports lighting control. Commercially available DALI EBGs
(electronic ballasts) can be connected.
Depending on the type, PXC3 series room automation stations can be operated
with TX-I/O devices and devices with KNX PL-Link.
DALI device type
0
7
1
3
5
4
2
6
8
9
10
*)
Partly supported means that basic functions are supported like with type 0, but
no further type specific functions.
**) In Desigo V6 and later
PXC3.E...
Room automation stations
Description
Fluorescent Lamps
Switching Function
Self-contained Emergency Lighting
Low Voltage Halogen Lamps
Conversion digital into D.C. Voltage
Incandescent Lamps
HID Discharge Lamps
LED Modules
Colour Control
Sequencer
Optical Control
Supported
Yes
Yes
Yes **)
Partly *)
Partly *)
No
No
Yes **)
No
No
No
3 / 12