Power Considerations - ABB AMVAC Installation And Operation Manual

Medium voltage vacuum circuit breakers
Hide thumbs Also See for AMVAC:
Table of Contents

Advertisement

E
C
LECTRONIC
ONTROL

POWER CONSIDERATIONS

The control board power supply recharge unit adapts any voltage within the specified range of the board to
maintain 80 V across the capacitors. The following voltage thresholds must be reached to complete the speci-
fied operations:
1. The capacitor voltage threshold for an Open operation is 49 volts.
2. The capacitor voltage threshold for a Close-Open operation is 72.5 volts.
3. The capacitor voltage threshold for a Open-Close-Open operation is 78 volts.
CAPACITOR CHARGE
Energy sufficient for O-CO operations
Energy sufficient for CO operations
Energy sufficient for O operations
Energy insufficient for any operation
Capacitor Life
The standard 0.1 Farad Electrolytic capacitors are designed to be operated in the temperature range of --40°
F to 185°F (--40°C to 85°C). The end-of-life corresponds to the point at which the capacitance decreases by
20% or more.
It is recommended that the replacement of capacitors be performed every 15 years for tropical climates and
20 years for an average yearly temperature of less than 122°F.
40
APPENDIX C
B
OARD
CIRCUIT BREAKER POSITION
CLOSE
Open allowed
Open allowed
Open allowed
Blocked in closed position or CB
opened (depending on dip switch
setting - I1004)
Apx. Table 3 CB Operations Vs. Available Capacitor Charge
1VAL050601-MB Rev C
OPEN
Close allowed
Close allowed
Blocked in open position
Blocked in open position