Drain Hose Installation - Samsung DH094EAM Installation Manual

Duct-type air conditioner cool and heat
Hide thumbs Also See for DH094EAM:
Table of Contents

Advertisement

Drain hose installation

Cable-Tie
Insulation drain
Indoor
Unit
Insulation drain
Drain Socket
pipe
C C
A A
U U
T T
I I
O O
N N
C C
A A
U U
T T
I I
O O
N N
Must fit tightly against
body without any gap.
C C
A A
U U
T T
I I
O O
C C
A A
U U
T T
I I
O O
When not installing the drain pump
Do not give the hose upward gradient after
the connection port.
This will cause water to flow backwards when
the unit is stopped, resulting in water leaks.
Upward gradient
Do not apply force to the piping on the unit side
when connecting the drain hose. The hose should
not be allowed to hang loose from its connection to
the unit. Fasten the hose to a wall, frame or other
support as close to the unit as possible.
12
E-
Care must be taken when installing the drain hose for the indoor unit
to ensure that any condensate water is correctly drained outside. The
drain hose can be installed to the right or left side of the base pan.
1
Remove the rubber cap located on the side of the base pan depending on
the situation.
2
Install the drain hose so that its length can be as short as possible.
Internal diameter of the drain hose should be the same or slightly
bigger than the external diameter of the drain port.
N N
o o
t t
e e
N N
o o
t t
e e
3
Wrap the drain hose with the insulation drain pipe, the insulation A as shown in
figure and secure them. And wrap the other drain tube outlet with the insulation
B provided.
N N
N N
Ceiling
Support pieces
Ceiling
Give a 3mm slant to the drain hose for proper drainage of
condensate.
Secure the drain hose with the cable-tie not to be separated
from the unit.
When installing the drain pump
The maximum height of drain pump hose is
75cm or less. If it is raised higher than 75cm,
there can be water leaks.
75cm or less
Ceiling

Advertisement