Download Print this page

Samsung MCM-A200 Installation Manual page 10

System air conditioner
Hide thumbs Also See for MCM-A200:

Advertisement

Centralized Controller Installation(cont.)
10
E-
If the wired remote controller and the centralized controller
is used at the same time, refer to the table below.
Wired Remote
Master Mode
Controller
(No.4 DIP Switch "OFF")
The wired remote controller
Centralized
has priority over the
controller
centralized controller.
When using the centralized
controller and the wired
remote controller, the air
conditioner will run in the
Level 0
mode selected when the
unit was last used. (The
wireless remote controller
cannot be used.)
The wired remote controller
is the only controller that
can be used when the
Level 1
centralized controller is
powered on. (The wireless
remote controller cannot be
used.)
The air conditioner can only
be operated with the
Level 2
centralized controller.
(The wired/wireless remote
controller cannot be used.)
N N
o o
t t
e e
Refer to the wired remote controller section of the
N N
o o
t t
e e
Installation Manual for information about the
MASTER MODE and SLAVE MODE.
Slave Mode
(No.4 DIP Switch "ON")
The wired remote controller
does not have priority over
the centralized controller.
When using the wired /
wireless remote controller,
the air conditioner will run in
the mode selected when the
unit was last used.
The wired/wireless remote
controller can be used when
the centralized controller is
powered on.
The air conditioner can only
be operated with the
centralized controller.
(The wired/wireless remote
controller cannot be used.)

Advertisement

loading

This manual is also suitable for:

A200uA201uMcm-a201