Sg Burner Setup - QHT Air Compressor User Manual

Direct venting systems for b-10 and sg oil fired boilers
Table of Contents

Advertisement

BURNER MANUFACTURER
NX (NEC 1201, 1202)
Boiler Model
Burner Model
Firing Rate
Insertion Depth
Nozzle
Spray Pattern
Pump Pressure
Head Type
Head Position
BURNER MANUFACTURER
BF3 and BF5
Boiler Model
Burner Model
Firing Rate
Insertion Depth
Nozzle
Spray Pattern
Pump Pressure
Turbulator
Air Gate
BURNER MANUFACTURER
Pioneer
Boiler Model
Burner Model
Firing Rate
Insertion Depth
Nozzle
Spray Pattern
Pump Pressure
Head Setting
Air Setting
* - These burners may not be used in Canada on Biasi equipment

3.2 SG Burner Setup

Beckett
SG-2*
SG-3*
NEC - 1201
NEC - 1202
0.65
1.00
3.5"
6.0"
o
.50 X 60
.75 X 60
hollow
solid
180 psi
180 psi
6 slot
9 slot
1.50
3.50
Riello
SG-2
SG-3
BF-3
BF-5
0.65
1.00
5.0"
5.0"
.55 X 70
.85 X 60
solid
solid
145 psi
145 psi
0
4.5
4.0
SG-2
SG-3
P-1 FV
P-1 KA
.65
1.00
3.5"
3.5"
0.5 X 80
0.75 X 70
solid
solid
200
200
6
3
12.0
11.5
SG-4*
NEC - 1202
1.30
6.0"
o
o
1.00 X 60
solid
180 psi
9 slot
4.25
SG-4
BF-5
1.30
5.0"
1.10 X 80
solid
145 psi
0
2
5.6
Heat Wise
SG-4
P-2 KA
1.30
3.5"
1.00 X 80
Semi Solid
200
3
11.5
12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B10-3B10-4B10-5B10-6B-13B-14 ... Show all

Table of Contents