Reverse Condensate Drains - Lennox LGH480 Installation Instructions Manual

Gas and cooling packaged units (35, 40, 45, & 50 ton)
Table of Contents

Advertisement

Reverse Condensate Drain Pan
Unit is shipped from the factory with the condensate drain
facing the front of the unit. Reverse drain pan when needed
as follows:
1- Remove blower door on front of unit. See figure 8 and 9.
FRONT MULLION
BLOWER DOOR
FIGURE 8
REMOVE BLOWER DOOR
BLOWER
DOOR
FIGURE 9
2- Remove and retain the patch plate on the front mullion.
3- Remove front mullion.
4- Remove and retain three screws securing drip shield.
See figure 10.
5- Locate the patch plate on the back mullion. Remove the
patch plate and install on the front mullion.
6- Remove back mullion.
7- Install patch plate from the front mullion on the back
mullion. Position the patch plate in the same location as
the previous patch plate.
REMOVE
SCREWS
Page 10
REMOVE SCREWS SECURING DRIP SHIELD
AND DRAIN PAN
REMOVE
SCREWS
FIGURE 10
8- Remove and retain three screws securing drip shields
on back side of unit. See figure 11. Remove long drip
shield.
9- Push the drain pan downward and remove from unit.
10- Rotate the drain pan and reinstall.
11- Reinstall long drip shield with retained screws.
12- Replace mullions and blower door.
REMOVE SCREWS SECURING DRIP SHIELD
AND DRAIN PAN
REMOVE
SCREWS
LONG DRIP
SHIELD
FIGURE 11
LGH/LCH420, 480, 540, 600
LONG DRIP
SHIELD
BACK DRIP
SHIELD