Refrigeration Cycle Diagram - LG LT-C1260CL Service Manual

Ceiling cassette air conditioner
Table of Contents

Advertisement

Refrigeration Cycle Diagram

INDOOR UNIT
HEAT
EXCHANGE
(EVAPORATOR)
LIQUID SIDE
2-WAY VALVE
GAS SIDE
3-WAY VALVE
Pipe Size
Capacity
GAS LIQUID
12K Btu/h
1/2"
1/4"
• Rated performance for refrigerant line length of: 7.5m
• If 12K Capacity is installed at a distance of 15m, 225g of refrigerant
should be added ....................................................(15-7.5) x 30g
OUTDOOR UNIT
CHECK VALVE
(Heating Model only)
CAPILLARY TUBE
ACCUMU
LATOR
COMPRESSOR
Elevation (m)
Length (m)
Max.
Max.
Rated
Rated
7.5
15
5
–8–
HEAT
EXCHANGE
(CONDENSER)
REVERSING
VALVE
(Heating Model Only)
* Additional
refrigerant
(g/m)
7
30
COOLING
HEATING