3.5 Dryer Transportation or Long-Term Storage
•
Close inlet and outlet valves, switch off the devices (S1) and (ON/OFF), and disconnect power.
•
Depressurize the air circuit using the condensate trap TEST button & remove the fill port plug to vent the reservoir.
•
Drain the reservoir tank into a suitably sized container by removing right side panel (B) & turning drain valve (A) counter-
clockwise.
•
Replace the fill port plug & close the drain valve (A) by turning clockwise.
4.0 MAINTENANCE
4.1 Weekly
•
Visually inspect for proper condensate drain operation.
4.2 Monthly
•
Isolate the dryer from the compressed air system by closing inlet & outlet valves and release pressure.
•
Clean or replace condesate drain trap filter to remove any accumulated debris.
4.3 Semi-annually
•
Check compressor electrical current draw against amperage listed on the data plate.
•
Remove power from the dryer and clean condenser finned surfaces with compressed air jet.
5.0 EQUIPMENT DATA
Model
Capacity (scfm)*
Compressor Power (HP)
Power Supply (V/Ph/Hz)
Rated Current (A)
Full Load Current (A)
Refrigerant Type
Refrigerant Charge (LBS)
Connection Size F (NPT)
Weight (lbs)
Max. Air Inlet (°F)
Max. Ambient (°F)
Max. Pressure (psig)
*Rated capacity @ air inlet of 100°F & 100 psig, 100°F ambient & 33 – 39° F leaving dewpoint
General Air Division
•
www.PSBINDUSTRIES.com
•
G5C-18
G5C-30
G5C-50
18
30
60
1/6
1/4
1/3
115/1/60
115/1/60
115/1/60
1.1
3.7
5.2
2
4.6
6.8
R-134a
R-134a
R-134a
0.66
0.79
1.21
1/2
1/2
3/4
66
77
119
113
113
113
104
104
104
230
230
230
1202 West 12th Street, Erie, PA. 16501
•
psb@genair.net
•
G5C-75
G5C-100
G5C-120
75
100
120
1/2
¾
1
115/1/60
115/1/60
115/1/60
6.8
8.1
9.2
8
9.8
11
R-134a
R-134a
R-134a
1.21
1.21
1.32
3/4
¾
1-1/2
132
141
203
113
113
113
104
104
104
230
230
230
5/16
G5C Dryers
G5C-150
G5C-200
G5C-250
150
200
250
1-1/2
1-1/2
2
230/1/60
230/1/60
230/1/60
7.5
7.5
8.5
8.7
10.5
12.5
R-134a
R-134a
R-134a
1.75
2.16
2.0
1-1/2
1-1/2
1-1/2
232
232
247
113
113
113
104
104
104
230
230
230
Cod. 710.062.01.00 – Rev.08 – 02.05.02
G5C-250
250
2
460/3/60
3
5.2
R-134a
2.0
1-1/2
247
113
104
230