Commissioning
Commissioning will normally be performed by our trained commissioning engineers.
Please note that prior to commissioning, it is the responsibility of the installing contractor to ensure the
following:
The LCMs must be connected and installed
Mains power must be available
Luminaires must be plugged in
The scene plate must be wired correctly and plugged into the LCM
The LCMs are factory set to a preset scene level as follows:
Scene
0
1
2
3
4
5
6
7
8
Commissioning is performed using the LCD programming handset. The following relates to the com-
missioning of all scenes accessible by the plate.
1.
Assign a Scene ID to the plate
2.
Ensure that the required LCM channel has an interface dependency on the Scene ID
3.
Program the Scene ID of the nearest plate to be the LCM master ID
4.
Assign the LCM channel to a circuit and give it the circuit ID. A circuit is any group of luminaires
that need to have the same brightness level.
5.
Select the scene on the scene plate. If it is scene 5-8, press and hold the button. If it is a room
divide scene, then ensure that the room divide contact is made.
6.
From the scene menu of the handset, select the circuit ID to be programmed.
7.
Adjust the brightness using the up/down buttons.
8.
When completed, press the scene button to store the value.
9.
Repeat above for all circuits and scenes.
10.
Any other parameter, such as fade time can be directly programmed from the handset by se-
lecting the scene first and sending the command.
The scene values can also be programmed using the keys for all scenes and circuits 1-8. See the users
guide for details.
Level
Off
100%
75%
50%
25%
50%
50%
50%
50%