1. VASCO Solar Introduction VASCO Solar Solar inverters come to power traditional pumping systems using photovoltaic energy. In this way it’s possible to convert old systems in renewable energy installations or to use the same AC pumps in the creation of independent, cost-saving and environmentally sustainable water systems.
2. Safety Instructions The manufacturer strongly suggests carefully reading this operation manual before using and installing its products Any operation (installation, maintenance and repair) must be carried out by trained, skilled, and qualified personnel. Failure to observe and follow the instructions in this manual may result in dangerous and potentially lethal electric shock. Pay attention to all standard safety and accident prevention regulations The device must be connected to main power supply via a switch to ensure the complete disconnection from the network before any operation on the VASCO...
Max I Typical motor P1 nom Vout Model [VDC] [VDC] [VAC] [VAC] [kW] VASCO Solar 212 120 – 650 > 320 3 x 230 3 x 230 VASCO Solar 409 320 – 850 > 560 3 x 400 3 x 400 VASCO Solar 412 320 –...
Page 6
3.1 Weight and dimensions SIZE 1 Weight Size Model [Kg] VASCO Solar 212 VASCO Solar 409 VASCO Solar 412 VASCO Solar 415 VASCO Solar 418 VASCO Solar 425 VASCO Solar 430 VASCO Solar 438 VASCO Solar 448 SIZE 2 VASCO Solar 465...
4. Electric wiring Power board VASCO Solar SIZE 1 DC Input: Motor output: 12 V dc auxiliary fans (wall mounting kit) LINE: L1, L3, GND MOTOR: U, V, W, GND VENT: +, - It is recommended to use cable It is recommended to use cable WARNING: respect the polarity.
Page 8
Power board VASCO Solar Size 2 Power supply: Motor output: INPUT: P.E. , + , - MOTOR: U, V, W, P.E. It is necessary to respect the polarity It is recommended to use cable lugs. It is recommended to use cable lugs. Cable stripping recommended for motor cables.
Page 9
Control board Analog inputs (10 or 15 Vdc): Digital outputs: RS485: 1. AN1: 4-20 mA: sensor 1 motor run signal: S+ 2. AN2: 4-20 mA: sensor 2 S- NO1, COM1: closed contact with motor 3. AN3: 4-20 mA / 0 - 10 Vdc ...
4.1 Protections The protections required upstream each VASCO Solar depends on the type of installation, and local regulations. We recommend to use 1000 VDC circuit breaker and, if possible, 1000 VDC surge protection. 4.2 Electromagnetic compliance To ensure electromagnetic compatibility (EMC) of the system, it is necessary to apply the following measures: ...
Page 11
5. VASCO Solar installation (SIZE 1) n.° 2 12 V DC fans. n.° 1 fans cover. n.° 2 fans cover fixing screws n.° 2 wall fixing brackets n.° 4 M5 screws for VASCO Solar fixing to the brackets ...
6. PV system sizing The pumping system must be designed considering daily flow rate required, total head and installation site. In particular, the choice of the pump must be carried out considering the average daily radiation. Once determined the required pump, must need to know: ...
VASCO Solar selection Being the rated motor voltage 400 VAC and the rated current 8.3 A, the most suitable model for the application is VASCO Solar 409. PV system sizing PV panels used: Wp = 240 W Vmp = 30 VDC ...
7.1.2 Pressure sensor VASCO Solar requires a pressure sensor with a linear output signal within the range 4 – 20 mA. The pressure transducer can be powered by any range of DC Voltage which includes the value 15 V dc. VASCO Solar accepts the signal of a second pressure sensor in order to: ...
8.2 Initial configuration When VASCO Solar is switched on for the first time, the initial setting menu is displayed for the initial setting of parameters to configure pump and system characteristics. If the initial setting procedure is not completed properly, it is impossible to run the pump. Initial setting procedure can be repeated if necessary.
8.3 Initial view When first powering the VASCO Solar, the display shows : release of display software (LCD = X.XX) and the release of inverter software (INV = X.XX) as shown below: LCD = X.XX INV = X.XX The following End User messages are displayed by pushing the scroll buttons: p is the pressure value read by the pressure transducer.
8.4 Menu view Pressing ENTER when you are in [MENU’ / ENT to access] in initial display, will display the following MENUs: Installer password required to enter level 1 (default 001) MENU’ Install. param. Advanced password required to enter level 2 (default 002) MENU’...
Page 18
parameter desciption Sensor minimum value. Min value sensor p = XX.X [bar] Maximum value allowed in the system. If the readen value goes over this value, an alarm occurs Max alarm value and the pump is stopped.
Page 19
parameter desciption To ensure proper operation of pressure control is recommended to place the sensor near the pump. To compensate the pressure loss in the pipes (proportional to flow) it is possible to vary the pressure set in a linear relation with respect to frequency.
Page 20
parameter desciption VASCO Solar powers the motor again; otherwise, VASCO Solar will stop the pump. This value represents the value Delta control drop below the set value required to restart the pump during control p = XX.X [bar] ramp.
Page 21
parameter desciption delay time with which the pumps DOL start after the variable speed Start delay AUX pump has reached the maximum frequency and the readen value t = XX [s] has fallen below set value – delta control.
Page 22
parameter desciption By selecting N.C. (normally closed) VASCO Solar runs the motor if the digital input 2 is closed; motor will be stopped if the digital input 2 is opened. By selecting N.A. (normally open) VASCO Solar runs the motor if the digital input 3 is open;...
Page 23
8.6 Advanced parameters All the advanced parameters, due to their importance, are already set during initial setup (cap. 6.2 Initial Configuration). However, it is always possible to modify individual parameters or modify the password 2: Parameters Default Description Open circuit voltage of PV strings. Please refer to PV panels datasheet. Open circuit Volt.
Page 24
85 % This parameter allows you to change the V / f characteristic with which VASCO Solar feeds the engine. The linear characteristic corresponds to constant torque with variable speed. The quadratic characteristic is V/f lin. --> quad. normally used with centrifugal pumps. The selection of torque characteristic should be done ensuring a smooth operation, a reduction of XXX % energy consumption and a lower level of heat and acoustic noise.
Page 25
Zero correction for analog input 4 (default 0-10V) Offset input 4 (10V x 00% = 0 V). x = XX.X [%] Pressing ENT allows the advanced level password (2st level) (default Change PASSWORD2 002) to be changed. 9. Protections and alarms Anytime a protection occurs a blinking message is displayed together with an audible alarm;...
Page 26
VASCO Solar before performing any maintenance. Check the transducer SENSOR FAULT Sensor error Check the wiring of transducer Check possible causes of reaching max value MAX. VALUE ALARM Measured value has reached the maximum Check the max alarm value setting value accepted by the system.
DECLARATION OF CONFORMITY In according with: Machine Directive 2006/42/EC EMC Directive 2004/108/CE Low Voltage Directive 2006/95/CE R&TTE Directive 1999/05/EU VASCO Solar is an electronic device to be connected to other electrical equipment with which it is to form individual units. It must, therefore, that the putting into service of this unit (with all its subsidiary equipments) to be performed by qualified personnel.
Page 28
NOTE Copyright NASTEC srl Nastec reserves the right to modify without previous notice any technical information contained in this document. Nastec srl, Via della Tecnica, 8, 36024, Mossano, Vicenza, Italy, Tel. +39 0444 886289, Fax +39 0444 776099, www.nastec.eu, info@nastec.eu...