3.4.3.1.
Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual
Table 3.4.2-1 IEC101 Slave OPC Client properties
Property / Para-
Value or Value range/ Default
meter
Basic
Maximum OPC
0...65535
Server Initialization
Default: 5
Time
Prog ID AE
ProgID DA
Time Zone Correc-
-720...720
tion
Default: 0
Station/Remote
Switch
Station/Remote
Do not check Station/Remote
Switch
switch position, command
always allowed.
Check Station/Remote switch
position.
Default: Do not check Sta-
tion/Remote switch position,
command always allowed.
Station/Remote
Reject commands if position
Switch Error
bad or unknown.
Allow commands if position bad
or unknown.
Default: Reject commands if
position bad or unknown
Configuring Channel Properties
Configuring IEC101 Balanced Channel properties
The IEC101 Balanced Channel properties that can be configured and value ranges for
them can be found in Table 3.4.3.1-1. The actual configuration by using the COM600
Station Automation Builder 600 (SAB600) is performed as described in 3.4.1, General
about configuring objects.
Description
Specifies the maximum time in seconds
that any connected (configured) OPC
Server requires to retrieve all its initial
data.
Instance identification of diagnostic OPC
alarm and event server.
Instance identification of diagnostic OPC
data access server.
The value of this property in minutes is
added to the synchronization time received
from an IEC101 master.
Specifies if a position check for the station
remote switch is going to be made.
Specifies what to do with commands if the
position of the switch is uncertain.
21