The Digiplex Control Panel can be programmed using
the
Paradox
Upload/Download
Windows® or manually by using a keypad as
described below. We highly recommend programming
the control panel with the Upload/Download software,
as it greatly simplifies the process and reduces the
potential of data errors.
3.1 U
/D
PLOAD
OWNLOAD
Remotely program the Digiplex Control Panels using
the Paradox Upload/Download Software, or perform
on-site programming. Please refer to section 13 for
details on how to set up the control panel to function
with the upload/download software.
3.2 P
ROGRAMMING
Use the supplied "Programming Guide" to keep track
of which sections were programmed and how. In
order to program anything in the Digiplex Control
Panel you must enter the programming mode.
To enter Control Panel Programming Mode:
Step 1 – Press & Hold [0] key
Step 2 – Key in [
INSTALLER CODE
Default is 000000
Step 3 – Key in 3-digit [
Every feature and or option is
programmed into a three-digit section
from [001] to [979].
Step 4 – Key in required [
The type of data required will be
detailed in the "Programming Guide"
and/or explained in the appropriate
section of this manual.
Most of the Digiplex Control Panel Options are
programmed using the Feature Select Method,
where each number from 1 to 8 corresponds to a
specific feature or option. Set these options by
turning the number corresponding to the feature
ON or OFF. The option is considered ON when
the number appears within the brackets on the
LCD keypad or when the number is illuminated
P R O G R A M M I N G M E T H O D
Software
S
OFTWARE
M
ODE
]
]
SECTION
]
DATA
on an LED Keypad. You turn options ON and
for
OFF by pressing the corresponding buttons on
the keypad. Press the keys as many times as
you need until all 8 options in the current
section are set. When the options are set, press
the [
ENTER
Certain sections may require the entry of one or
more Hexadecimal values from 0 to F:
[0] to [9] = values 0 to 9 respectively
[
] key = A
STAY
[
] key = B
FORCE
[
] key = C
ARM
Certain sections may require the entry of a 3-
digit Decimal value from 000 to 255.
After entering the required data, the control panel
will save the data and automatically advance to the
next section, or press the [
whatever data has been entered and automatically
advance to the next section. Press the [
to revert to the preceding step, unless you are entering
data, in which case it will erase the current data entry.
To enter the Module Programming Mode:
Step 1 – Press & Hold [0] key
Step 2 – Key in [
Default is 000000
Step 3 – Key in section [953]
Step 4 – Key in 8-digit [
module you wish to program
Step 5 – Key in 3-digit [
[
DATA
desired module for details.
3.3 P
ROGRAMMING
The control panel will redirect all programming to the
selected module. To exit the Module Programming
Mode, press the [
needed to return to the desired screen. Please note
that a module's serial number can be located on the
module's PC board or it may already be recorded in
the module's Programming Guide.
- 12 -
] or [p p ] key to save.
[
DISARM
[
] key = E
BYP
[
] key = F
MEM
ENTER
]
INSTALLER CODE
SERIAL NUMBER
] & required
SECTION
] Refer to installation manual of
B
M
US
] key as many times as
CLEAR
] key = D
] key to save
] key
CLEAR
] of the
ODULES

Advertisement