Product Description - GE G60 Instruction Manual

Generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

G60 Generator Protection System
Chapter 2: Product description

Product description

This chapter outlines the product, order codes, and specifications.
2.1 Product description
The G60 Generator Protection System is part of the Universal Relay (UR) series of products. It is a microprocessor-based
relay that provides protection, monitoring, control, and recording functions for alternating current (AC) generators driven
by steam, gas, or hydraulic turbine. Current, voltage, and frequency protection are provided along with fault diagnostics.
Breaker fail function is provided for up to four breakers.
Voltage, current, and power metering are built into the relay as standard features. Current parameters are available as
total waveform root mean square (RMS) magnitude, or as fundamental frequency only RMS magnitude and angle (phasor).
Diagnostic features include an event recorder capable of storing 1024 time-tagged events, oscillography capable of
storing up to 64 records with programmable trigger, content, and sampling rate, and data logger acquisition of up to 16
channels, with programmable content and sampling rate. The internal clock used for time-tagging can be synchronized
with an IRIG-B signal, using the Simple Network Time Protocol (SNTP) over the Ethernet port, or using the Precision Time
Protocol (PTP). This precise time stamping allows the sequence of events to be determined throughout the system. Events
can also be programmed (via FlexLogic
equations) to trigger oscillography data capture that can be set to record the
measured parameters before and after the event for viewing on a computer PC. These tools significantly reduce
troubleshooting time and simplify report generation in the event of a system fault.
Several options are available for communication. An RS232 port (USB port with the graphical front panel) can be used to
connect to a computer to program settings and monitor actual values. The rear RS485 port allows independent access by
operating and engineering staff. It can be connected to system computers with baud rates up to 115.2 kbps. All serial ports
use the Modbus RTU protocol. The IEC 60870-5-103 protocol is supported on the RS485 interface. IEC 60870-5-103, DNP,
and Modbus cannot be enabled simultaneously on this interface. Also only one of the DNP, IEC 60870-5-103, and IEC
60870-5-104 protocols can be enabled at any time on the relay. When the IEC 60870-5-103 protocol is chosen, the RS485
port has a fixed even parity and the baud rate can be either 9.6 kbps or 19.2 kbps. The 100Base-FX or 100Base-TX Ethernet
interface provides fast, reliable communications in noisy environments. The Ethernet port supports IEC 61850, IEC 61850-
90-5, Modbus/TCP, TFTP, and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access to the relay via any
standard web browser (G60 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port. The Ethernet
port also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when purchased as an option.
Secure Routable GOOSE (R-GOOSE) is supported with software options.
Settings and actual values can be accessed from the front panel or EnerVista software.
The G60 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
2-1

Advertisement

Table of Contents
loading

Table of Contents