Gas Piping

Gas supply piping should not allow more than 0.5"W.C.
drop in pressure between gas meter and unit. Supply gas
pipe must not be smaller than unit gas connection
CAUTION
If a flexible gas connector is required or allowed by the
authority that has jurisdiction, black iron pipe shall be
installed at the gas valve and extend outside the furnace
cabinet. The flexible connector can then be added
between the black iron pipe and the gas supply line.
Gas Supply
WARNING
Do not over torque (800 in-lbs) or under torque (350 in-
lbs) when attaching the gas piping to the gas valve.
1 - This unit is shipped standard for left or right side
installation of gas piping (or top entry in horizontal
applications). Connect the gas supply piping into
the gas valve. The maximum torque is 800 in lbs
and minimum torque is 350 in lbs when attaching
the gas piping to the gas valve.
Nominal
Internal
Iron Pipe
Diameter
Size Inches
inches
(mm)
(mm)
1/2
.622
(12.7)
(17.799)
3/4
.824
(19.05)
(20.930)
1
1.049
(25.4)
(26.645)
1-1/4
1.380
(31.75)
(35.052)
1-1/2
1.610
(38.1)
(40.894)
2
2.067
(50.8)
(52.502)
2-1/2
2.469
(63.5)
(67.713)
3
3.068
(76.2)
(77.927)
NOTE - Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specific gravity gas.
Gas Pipe Capacity - ft3/hr (m3/hr)
10
20
30
(3.048)
(6.096)
(9,144)
172
118
95
(4.87)
(3.34)
(2.69)
360
247
199
(10.19)
(7.000)
(5.63)
678
466
374
(19.19)
(13.19)
(10.59)
1350
957
768
(38.22)
(27.09)
(22.25)
2090
1430
1150
(59.18)
(40.49)
(32.56)
4020
2760
2220
(113.83)
(78.15)
(62.86)
6400
4400
3530
(181.22)
(124.59)
(99.95)
11300
7780
6250
(319.98)
(220.30)
(176.98)
2 - When connecting the gas supply piping, consider
factors such as length of run, number of fittings, and
furnace rating to avoid excessive pressure drop.
Table 6 lists recommended pipe sizes for typical
applications.
3 - The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb
waiters, or elevator shafts.
4 - The piping should be sloped 1/4 inch (6.4 mm) per
15 feet (4.57 m) upward toward the meter from the
furnace. The piping must be supported at proper
intervals [every 8 to 10 feet (2.44 to 3.01 m)] with
suitable hangers or straps. Install a drip leg in
vertical pipe runs to the unit.
5 - A 1/8" N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See figure 31.
6 - In some localities, codes may require the installation
of a manual main shut-off valve and union (furnished
by the installer) external to the unit. The union must
be of the ground joint type.
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquified petroleum gases.
NOTE - If emergency shutoff is necessary, shut off the
main manual gas valve and disconnect main power to the
furnace. The installer should properly label these devices.
TABLE 6
Length of Pipe - feet (m)
40
50
60
(12,192)
(15.240)
(18.288)
81
72
65
(2.29)
(2.03)
(1.84)
170
151
137
(4.81)
(4.23)
(3.87)
320
284
257
(9.06)
(8.04)
(7.27)
657
583
528
(18.60)
(16.50)
(14.95)
985
873
791
(27.89)
(24.72)
(22.39)
1900
1680
1520
(53.80)
(47.57)
(43.04)
3020
2680
2480
(85.51)
(75.88)
(70.22)
5350
4740
4290
(151.49)
(134.22)
(121.47)
Page 21
IMPORTANT
70
80
90
(21.336)
(24.384)
(27.432)
60
56
52
(1.69)
(1.58)
(1.47)
126
117
110
(3.56)
(3.31)
(3.11)
237
220
207
(6.71)
(6.23)
(5.86)
486
452
424
(13.76)
(12.79)
(12.00)
728
677
635
(20.61)
(19.17)
(17.98)
1400
1300
1220
(39.64)
(36.81)
(34.55)
2230
2080
1950
(63.14)
(58.89)
(55.22)
3950
3670
3450
(111.85)
(103.92)
(97.69)
100
(30,480)
50
(1.42)
104
(2.94)
195
(5.52)
400
(11.33)
600
(17.00)
1160
(32.844)
1840
(52.10)
3260
(92.31)