Responding To Error Display On The Remote Controller - Mitsubishi Electric PQHY-P200YLM-A Service Handbook

Hide thumbs Also See for PQHY-P200YLM-A:
Table of Contents

Advertisement

[ IX Troubleshooting ]

[2] Responding to Error Display on the Remote Controller

1. Error Code
0403
Serial communication error
2. Error definition and error detection method
Serial communication error between the control board and the INV board on the compressor.
Detail code 01: Between the control board and the INV board
3. Cause, check method and remedy
(1) Faulty wiring
Check the following wiring connections.
1) Between Control board and INV board
Control board
INV board
CN61
CN2
CN4
CN4(or CN43)
CN2
CN5V
(2) INV board failure and Control board failure
Replace the INV board or the Fan board when the power turns on automatically, even if the power source is reset.
Refer to section -6- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.
1. Error Code
0403
Panel communication error (Indoor unit)
2. Error definition and error detection method
This error is detected when indoor units cannot successfully receive the signals from the Auto filter cleaning unit for one min-
ute.
3. Cause, check method and remedy
(1)
Incorrect switch setting on the indoor unit cir-
cuit board
(2)
Power wire that connects the circuit board on
the indoor unit and the circuit board on the
cleaning unit is loose.
(3)
Communication wire that connects the circuit
board on the indoor unit and the circuit board
on the cleaning unit is loose.
(4)
Panel transceiver circuit fault (cleaning unit)
(5)
Panel transceiver circuit fault (indoor unit)
(6)
Electrical interference on the cleaning unit's
communication cable
HWE15060
Cause
Check method and remedy
Check SW3-3 on the indoor unit circuit board
Set SW3-3 to ON only when connecting an auto filter cleaning
unit.
Check the LED1 (cleaning unit circuit board (microcomputer
power)).
Lit: Power is supplied properly.
Unlit: Check for loose or disconnected power wire between the
indoor unit circuit board (CNAC) and the cleaning unit circuit
board (CN3A).
Check the LED4 (cleaning unit circuit board (communication)).
Blinking: Normal communication
Unlit: Check for loose or disconnected communication wire be-
tween the indoor unit circuit board (CN3G) and the cleaning unit
circuit board (CN3G).
If the LED blinks at irregular intervals (normally blinks at 0.5-sec-
ond intervals), electrical interference is suspected.
Check the items above, turn the power off, and turn the power
back on. If the error persists, replace either the cleaning unit cir-
cuit board or the indoor unit circuit board.
- 271 -
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents