Installing A 1 (Ru) Chassis In A Two-Post Rack - Cisco Nexus 36180YC-R Hardware Installation Manual

Nexus 3600 series
Table of Contents

Advertisement

Installing a 1 (RU) Chassis in a Two-post Rack

c) Holding the chassis level, insert two screws (10-32 or 12-24, depending on the rack type) in each of the two front
rack-mount brackets (using a total of four screws) and into the cage nuts or threaded holes in the vertical rack-mounting
rails (see the following figure).
Figure 6: Attaching the Switch to the Rack
1
Fasten the chassis to the front of the rack
with two 10-32 or 12-24 screws on each
side.
2
Front-mount bracket.
d) Tighten the 10-32 screws to 20 in-lb (2.26 N·m) or tighten the 12-24 screws to 30 in-lb (3.39 N·m).
Installing a 1 (RU) Chassis in a Two-post Rack
This section describes the rack installation for the Cisco Nexus 3000 series switch into a two-post rack.
To install a switch, you must attach mounting brackets to the switch and secure the switch to the rack.
Installation in racks other than 19-inch racks requires a bracket kit not included with the switch.
Cisco Nexus 3600 Hardware Installation Guide
14
3
Mounting rails on rack or cabinet posts.
Installing the Chassis