10. If redundant ac power is not used, test the grounding continuity between a conductive area on the
SAN Volume Controller frame and the ground pin on the plug of the uninterruptible power-supply
input-power cable.
11. If redundant ac power is used, test the grounding continuity between a conductive area on the SAN
Volume Controller frame and the ground pin on the plug of the main power cable of the redundant
ac-power switch. If the test is successful, test the grounding continuity between a conductive area on
the SAN Volume Controller frame and the ground pin on the plug of the backup power cable of the
redundant ac-power switch. Both tests must be successful.
12. After you have completed testing the grounding continuity, perform one of the following procedures,
depending on the outcome of the test.
v If the test is successful, reconnect any cables that were removed, and power on any
uninterruptible power-supply units and SAN Volume Controller nodes that were powered off.
v If the test was not successful, ensure that all cables are securely connected. If the test still fails, test
the individual system components. Before you test the individual components, remove all cables
from the components. If any component test fails, replace the component. After each component
has been tested and the failing ones have been replaced, repeat the complete system test by
returning to step 1 on page xviii.
Test the components in the following order:
a. The SAN Volume Controller node, from the frame to the ground pin of the input power
receptacle
b. The uninterruptible power supply from the ground pin of the input power receptacle to the
ground conductor of the output power receptacle
c. If used, the redundant ac-power switch from the ground pin of the main input power
receptacle to the ground conductor of the output power receptacle, and from the ground pin of
the backup input power receptacle to the ground conductor of the output power receptacle
d. The SAN Volume Controller node to uninterruptible power-supply power-cable assembly,
between the two ground conductors of the power cable
e. The uninterruptible power-supply input-power cable, between the two ground conductors of
the power cable
f. If used, the redundant ac-power switch main input-power cable, between the two ground
conductors of the cable
g. If used, the redundant ac-power switch backup input-power cable, between the two ground
conductors of the cable

Inspecting the uninterruptible power supply for unsafe conditions

Ensure that you take the time to inspect the uninterruptible power supply for unsafe conditions.
Consider the following conditions and their potential safety hazards:
Electrical hazards (especially primary power)
Primary voltage on the frame can cause serious or lethal electrical shock.
Explosive hazards
A bulging capacitor can cause serious injury.
Mechanical hazards
Loose or missing items (for example, nuts and screws) can cause serious injury.
Use caution when working in a potential safety hazard that is not covered in the safety checks. If unsafe
conditions are present, determine how serious the hazards are and whether you can continue before you
correct the problem.