APPENDIX A
Appendices
APPENDI X A Fl e xAnal o g and Fl e xI n t e ger Par a met e r s A.1Parameter Lists
A FlexAnalog parameter is an analog parameter.
FlexAnalog items are also viewable in a web browser. Enter the IP address of the UR, access the Device Information
Menu option, then the FlexAnalog Parameter Listing option. Entries displayed online depend on order code.
Table A–1: FLEXANALOG DATA ITEMS (Sheet 1 of 23)
ADDRESS
FLEXANALOG NAME
5728
Stator Diff Iad
5730
Stator Rest Iar
5732
Stator Diff Ibd
5734
Stator Rest Ibr
5736
Stator Diff Icd
5738
Stator Rest Icr
5744
Stator Gnd Vn 3rd
5746
Stator Gnd Vn+V0 3rd
5748
Stator Gnd V0 3rd
5760
Sns Dir Power 1
5762
Sns Dir Power 2
5792
RGF 1 Igd Mag
5794
RGF 1 Igr Mag
5796
RGF 2 Igd Mag
5798
RGF 2 Igr Mag
5800
RGF 3 Igd Mag
5802
RGF 3 Igr Mag
5804
RGF 4 Igd Mag
5806
RGF 4 Igr Mag
5824
Field RTD 1 Value
5825
Field RTD 2 Value
5826
Field RTD 3 Value
5827
Field RTD 4 Value
5828
Field RTD 5 Value
5829
Field RTD 6 Value
5830
Field RTD 7 Value
5831
Field RTD 8 Value
5832
Field TDR 1 Value
5834
Field TDR 2 Value
5836
Field TDR 3 Value
5838
Field TDR 4 Value
5840
Field TDR 5 Value
5842
Field TDR 6 Value
5844
Field TDR 7 Value
5846
Field TDR 8 Value
5856
Freq Rate 1 Value
5860
Freq Rate 2 Value
5864
Freq Rate 3 Value
5868
Freq Rate 4 Value
6144
SRC 1 Ia RMS
6146
SRC 1 Ib RMS
GE Multilin
UNITS
DESCRIPTION
Amps
Stator differential phase A current (Iad)
Amps
Stator restraint phase A current (Iar)
Amps
Stator differential phase B current (Ibd)
Amps
Stator restraint phase B current (Ibr)
Amps
Stator differential phase C current (Icd)
Amps
Stator restraint phase C current (Icr)
Volts
Stator ground Vn third harmonic voltage
Volts
Stator ground Vn+V0 third harmonic voltage
Volts
Stator ground V0 third harmonic voltage
Watts
Sensitive directional power 1 actual value
Watts
Sensitive directional power 2 actual value
Amps
Restricted ground fault 1 differential ground current magnitude
Amps
Restricted ground fault 1 restricted ground current magnitude
Amps
Restricted ground fault 2 differential ground current magnitude
Amps
Restricted ground fault 2 restricted ground current magnitude
Amps
Restricted ground fault 3 differential ground current magnitude
Amps
Restricted ground fault 3 restricted ground current magnitude
Amps
Restricted ground fault 4 differential ground current magnitude
Amps
Restricted ground fault 4 restricted ground current magnitude
---
Field RTD 1 value
---
Field RTD 2 value
---
Field RTD 3 value
---
Field RTD 4 value
---
Field RTD 5 value
---
Field RTD 6 value
---
Field RTD 7 value
---
Field RTD 8 value
---
Field TDR 1 value
---
Field TDR 2 value
---
Field TDR 3 value
---
Field TDR 4 value
---
Field TDR 5 value
---
Field TDR 6 value
---
Field TDR 7 value
---
Field TDR 8 value
Hz/s
Frequency rate of change 1 actual value
Hz/s
Frequency rate of change 2 actual value
Hz/s
Frequency rate of change 3 actual value
Hz/s
Frequency rate of change 4 actual value
Amps
Source 1 phase A current RMS
Amps
Source 1 phase B current RMS
G30 Generator Protection System
A.1 PARAMETER LISTS

A.1.1 FLEXANALOG ITEMS

A-1
A