Local Panel

Local Panel
An alternate way of interacting with the Safeguard 400 Series controller is the local
panel. The controller has a local panel switch (ISOLATE), which has three
positions (0, SCA, SCB):

Status Presentation in Process Displays

To insert the Safeguard Status object in a process display:
1.
2.
3.
4.
5.
6.

System Status

The System Status Viewer aspect follows the basic principles of status presentation
for Safeguard Dual systems, that is, displaying combined status of SCA and SCB in
the Dual Object structure and displaying the individual status of SCA and SCB in
the Single Node Access structure.
22
The middle position (0) is normal where both SCA and SCB control the
outputs unless isolated for other reasons.
The two other position are marked SCA and SCB. Turning the switch to these
positions sets the related safety controller in local mode. When the safety
controller is in local mode the safety dialog is disabled except for the message
buffer scrolling keys.
Create and upload a Safeguard dual system in the Control Structure.
Insert the two MMCX3 objects in the Functional Structure where appropriate.
Create and edit a Graphic Display.
In the Graphic Builder, open the Object Browser.
a.
Browse to the first of two Safeguard Status objects (MMCX3) in the
Functional structure and select the graphic element aspect NameSG02.
b.
Select the other Safeguard Status object and insert the same graphic
element for this as well.
Position the two graphic elements as convenient, save and deploy the display.
Exit the Display Builder.
Section 2 Operation
3BNP004849-600