Further details regarding the individual steps
2. If the pre-charge pressure of the dia-
phragm expansion vessel is lower
than the value calculated according
to the adjacent formula, top up with
sufficient nitrogen to achieve this
value.
3. Refill with water until the filling pres-
sure is 0.2 bar higher than the pre-
charge pressure of the diaphragm
expansion vessel when the system is
cold.

Cleaning the sight glass in the boiler door

A
B

Closing the boiler door

1. Tighten the screws on the boiler door
evenly and diagonally.

Checking the thermal insulation

Check the thermal insulation fit and
adjust if required.

Checking the mixer for ease of operation and leaks

1. Remove the motorised lever from the
mixer handle.
Commissioning, inspection, maintenance
(cont.)
4. Mark this value on the pressure
gauge as the minimum filling pres-
sure.
Check gaskets A and hose connection
B for leaks.
2. Install the gas supply pipe and check
for tightness.
2. Check the mixer for ease of opera-
tion.
13