Siemens 7SR12 Argus Manual page 351

Overcurrent relay energy management
Hide thumbs Also See for 7SR12 Argus:
Table of Contents

Advertisement

46BC Setting
20%
25%
30%
35%
40%
46BC Setting
3P balanced current (A)
Apply 1A 1P unbalance current without 3P balanced current. Measure 46BC operating time.
46BC Delay setting
3.4.1.1
Element Blocking
The Broken Conductor element can be blocked by Binary Input Inhibit. This functionality should be checked.
©2017 Siemens Protection Devices Limited
Element
46BC
7SR11 & 7SR12 Commissioning and Maintenance Guide
1P unbalance current
(% of 3P current)
75%
100%
129%
161%
200%
1P unbalance current (A)
Measured
Measured Unbalance
current
BI Inhibits
Chapter 6 Page 67 of 72