Functions
2.17 Auxiliary Functions
2.17.3.1

Display of Measured Values

Table 2-16
Measured
sekun-
Values
dary
, Ι
, Ι
,
Ι
Ι
A
B
C
sec.
, Ι
Ι
1
2
= 3 ·Ι
Ι
Ι
E
0
e sec.
(calculated)
= measured
Ι
Ι
N
N sec.
value of Ι
-input
N
Ι
Ι
Ns
Ns sec.
Table 2-17
Parameter
CT PRIMARY
CT SECONDARY
Depending on the type of device ordered and the device connections, some of the operational measured
values listed below may not be available.
The ground current Ι
[erdstrom-020315-wlk, 1, en_US]
In addition, the following may be available:
Θ/Θ
thermal measured value of overload protection value for stator in % of the trip initiating over-
TRIP
temperature
Θ/Θ
thermal measured value of restart inhibit (rotor winding),
L TRIP
Θ
restarting limit of restart inhibit,
Restart
T
total time, before the motor can be restarted,
Reclose
Θ
to Θ
RTD 1
The calculation of the operational measured values is also performed during a fault. The values are updated in
intervals of > 0.3 s and < 1 s.
2.17.3.2

Transfer of Measured Values

Measured values can be transferred via the interfaces to a central control and storage unit.
The measuring range in which these values are transmitted depend on the protocol and, if necessary, addi-
tional settings.
Protocol
IEC 60870-5-103
206
Conversion formulae between secondary values and primary/percentage values
primary
Legend for the conversion formulae
Address
204
205
is either measured directly or calculated from the conductor currents.
N
temperature values at the RTD box.
RTD 12
Transmittable measuring range, format
0 to 240 % of the measured value.
Parameter
Ignd-CT PRIM
Ignd-CT SEC
FullScaleCurr.
C53000-G1140-C210-6, Edition 05.2016
%
Address
217
218
1102
SIPROTEC 4, 7SJ61, Manual