Dedicated Current Transformer Specifications - Panasonic KW1M-H User Manual

Eco-power meter
Table of Contents

Advertisement

8.10 Dedicated Current Transformer Specifications

●Clamp-on type
Model No
Primary side rated current
Secondary side rated
Current
Transform ratio
Ratio error
Hole Dia (mm)
Breakdown voltage (initial)
Insulation resistance
Functional
Vibration
resistance
Destructive
Shock
Functional
resistance
Destructive
Output protection level
Permissible
clamping frequency
Ambient temperature
Storage temperature
Ambient humidity
Weight (with relay cable)
●Through type
Model No
Primary side rated current
Secondary side rated
Current
Transform ratio
Ratio error
Hole Dia (mm)
Breakdown voltage (initial)
Insulation resistance
Functional
Vibration
resistance
Destructive
Functional
Shock
resistance
Destructive Min. 294m/ s
Output protection level
Ambient temperature
Storage temperature
Ambient humidity
Weight (with relay cable)
Note) Dedicated current transformers (CT) are dedicated for low voltage under 440V. They can not
be used for high voltage circuit. In case measuring high voltage circuit, make a 2-step
construction by combination of a commercial CT of secondary side current 5A for high
voltage and the dedicated CT for 5A.
AKW4801B
AKW4801C
5A / 50A
1.67mA /
16.7mA
3000:1
φ10
AC1000V/1min
(Between through hole
and output lead wire)
Min. 100MΩ (at DC500V) (Between through hole and output lead wire)
(initial)
10 to 55Hz (1 cycle/ minute) single amplitude of 0.15mm
10 to 55Hz (1 cycle/ minute) single amplitude of 0.375mm
2
Min. 98m/s
(4 times on X,Y and Z axes)
2
Min. 294m/ s
±7.5V with clamp element
-10 to +50℃ (without frost and non-condensing)
-20 to +60℃ (without frost and non-condensing)
30 to 85%RH (at 20℃ non-condensing)
Approx. 60g
AKW4506B
AKW4506C
50A / 100A
16.7mA / 33.3mA
3000:1
φ17
AC1000V/1min
(Between through hole and
output lead wire)
Min. 100MΩ (at DC500V) (Between through hole and output lead wire)
(initial)
10 to 55Hz (1 cycle/ minute) single amplitude of 0.15mm
10 to 55Hz (1 cycle/ minute) single amplitude of 0.375mm
2
Min. 98m/s
(4 times on X,Y and Z axes)
2
±7.5V with clamp element
-10 to +50℃ (without frost and non-condensing)
-20 to +60℃ (without frost and non-condensing)
30 to 85%RH (at 20℃ non-condensing)
Approx. 70g
AKW4802B
AKW4803B
AKW4802C
AKW4803C
100A
250A
33.3mA
125mA
3000:1
2000:1
±2.0% F.S.
φ16
φ24
(10 min. on X,Y and Z axes)
(1 hrs. on X,Y and Z axes)
(5 times on X,Y and Z axes)
Approx. 100 times
Approx. 90g
Approx. 200g
AKW4507B
AKW4507C
250A / 400A
125mA / 200mA
±1.0%F.S.
(10 min. on X,Y and Z axes)
(1 hrs. on X,Y and Z axes)
(5 times on X,Y and Z axes)
Approx. 200g
78
KW1M-H Eco-POWER METER
AKW4804B
AKW4804C
400A
200mA
2000:1
φ36
AC2000V/1min
(Between through hole
and output lead wire)
±3.0V with clamp element
Approx. 295g Approx. 450g
AKW4508B
AKW4508C
2000:1
φ36
AC2000V/1min
(Between through hole
and output lead wire)
±3.0V with clamp element
Approx. 215g
AKW4808B
AKW4808C
600A
200mA
3000:1
600A
200mA
3000:1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kw1m-h eco-power meterAkw1121

Table of Contents