Wired remote control

If an error occurs,
is displayed on the wired remote control.
If you would like to see an error code, press the Test button.
Display
E108
Error due to repeated communication address
E121
Error on room temperature sensor of indoor unit (Short or Open)
E122
Error on EVA IN sensor of indoor unit (Short or Open)
E123
Error on EVA OUT sensor of indoor unit (Short or Open)
E153
Error on float switch (2nd detection)
E154
Indoor fan error
E198
Error on thermal fuse of indoor unit (Open)
Communication error between indoor unit and outdoor unit (Pre tracking failure or when actual
E201
number of indoor units are different from the indoor unit quantity setting on the outdoor unit) Error
due to communication traking failure after initial power is supplied.
Communication error between indoor unit and outdoor unit (When there is no response from indoor
E202
units after tracking is completed)
Communication error between outdoor unit inv - main micom (For PF #4~#6 controller, error will be
E203
determined from the time when compressor is turned on)
E221
Error on outdoor temperature sensor (Short or Open)
E231
Error on outdoor COND OUT sensor (Short or Open)
E251
Error on discharge temperature sensor of compressor 1 (Short or Open)
E320
Error on OLP sensor (Short or Open)
E403
Compressor down due to freeze protection control
E404
System stop due to overload protection control
E416
System stop due to discharge temperature
E422
Blockage detected on high pressure pipe
E425
Reverse phase or open phase
E440
Heating operation restricted at outdoor temperature over Theat_high value [default: 30°C(86°F)]
E441
Cooling operation restricted at outdoor temperature below Tcool_low value [default: 0 °C(0 °F)]
E458
Fan speed error
E461
Error due to operation failure of inverter compressor
E462
System stop due to full current control
E463
Over current trip / PFC over current error
E464
IPM Over Current(O.C)
E465
Comp. Over load error
E466
DC-Link voltage under/over error
E467
Error due to abnormal rotation of the compressor or unconnected wire of compressor
E468
Error on current sensor (Short or Open)