Westinghouse 220VWH Manual page 13

Premier volume water heaters wbre**220 / 299 / 301 / 399 vwh series
Table of Contents

Advertisement

The water must be potable, free of corrosive chemicals, sand,
dirt, and other contaminates. It is up to the installer to ensure the
water does not contain corrosive chemicals or elements that can
damage the heat exchanger. Potable water is defined as drinkable
water supplied from utility or well water in compliance with EPA
secondary maximum contaminant levels (40 CFR Part 143.3) as
shown in the table below. If the water contains contaminants higher
than outlined by the EPA, water treatment is recommended and
additional, more frequent maintenance may be required.
If you suspect that your water is contaminated in any way,
discontinue use of the appliance and contact an authorized
technician or licensed professional.
Maximum
Contaminant
Allowable
Level
Total Hardness
(Commercial
120 mg/l
o
Use - 140
F and
(7 grains/gallon)
above water
temperature)
Aluminum
0.05 to 0.2 mg/l
Chloride
100 mg/l
Copper
1 mg/l
Iron
0.3 mg/l
Manganese
0.05 mg/l
Table 4 - Water Quality Specifications
*NOTE: It is recommended to clean heat exchanger at least once
a year to prevent lime scale buildup. Follow the maintenance
procedure in the Maintenance Section of this manual to clean the
heat exchanger.
Maximum
Contami-
Allowable
nant
Level
pH
6.5-8.5
Sulfate
205 mg/l
Total
Dissolved
500 mg/l
Solids (TDS)
Zinc
5 mg/l
Dissolved
15 mg/l or
Carbon
PPM
Dioxide (CO2)
WHL-053 Rev. 00 Rel. 003 Date 7.21.17
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

299vwh301vwh399vwh

Table of Contents