Auxiliary Relay Contacts; Accessories; Programming Requirements - Honeywell 14506873-001 Installation Instructions Manual

Intelligent air duct smoke detector housing
Table of Contents

Advertisement

Power Supply Electrical Ratings For 14506873-001
Power
120 VAC (102 - 132)
Requirements
mA rms MAX.
Device
Standby
14506873-001
44
BRKPA400*
--
SSDRA400ZA*
--
SSDRTS451/SSDRTS451KEY*
--
SSDRTS451**/SSDRTS451KEY
11.5
24V output maximum load is 80 mA; auxiliary alarm output maximum load is 20 mA.

Auxiliary Relay Contacts

minimum contact current must be greater than 500 mA at 24 VDC
10 amps maximum at 30 VDC
10 amps maximum at 250 VAC

Accessories

Remote LED
Piezo Alert Sounder
Replacement Filters
Magnet
End Plug For Sampling Tube
Installation Kit (Parts bag)
Photoelectronic Replacement Screen
Ionization Replacement Screen
Sensitivity Test Kit
Ionization Cover Removal Tool
Remote Test Station
SAMPLING (INLET) TUBES
TUBE
OUTSIDE DUCT WIDTH
SSDST-1.5
1 to 2 ft.
SSDST-3
2 to 4 ft.
SSDST-5
4 to 8 ft.
SSDST-10
8 to 12 ft.
Programming Specifications/Requirements For Intelligent System Control Panels.
NOTE: Models TC807A and TC806A can be used with the 14506873-001 if the following constraints are observed:
1. There may be a limit to the number of devices per zone that can have their LEDs latched on. The number of devices
is determined by the control panel and its ability to supply LED current. If more than the maximum number of devices
are on the same loop, Do NOT use the 14506873-001 for control purposes. Control for duct applications would need
to come directly from the control panel or by using control modules. If sensor models TC807A1036, TC807A1044,
TC806A1037, or TC806A1052 are used, the constraints above do not apply.
2. The duct control circuitry (auxiliary relay contacts and auxiliary alarm output) may change states if the sensor is test-
ed and the LED is turned on for more than 4 seconds. If the LED is latched on for less than 4 seconds, the control
circuitry of the 14506873-001 will NOT operate.
3. The panel must not continuously poll the same unit for more than 4 seconds or the auxiliary relay and auxiliary alarm
output may switch states. After 4 seconds of continual polling of a device, the panel must wait a minimum of 100ms
before polling or communicating to that same device.
4. Communications must not cease for more than 3 seconds without an additional clock pulse (after Pulse Width 5) to
turn off the LED on the sensor.
5. To allow the auxiliary relay and auxiliary alarm output to return to a standby condition, (after being in alarm) the panel
must wait a minimum of 100ms after turning off the sensor LED before communicating with that device again.
H500-03-00
240 VAC (204 - 264)
mA rms MAX.
Alarm
Standby
Alarm
30
52
25
1.5
3
--
1
1.5
--
1
1.5
--
6.5
13
5.5
Part No.
SSDRA400Z
SSDPA400
SSDF360500
SSDM0204
SSDP482100
SSDA2650-01
SSDRS24
SSDRS14
SSDMOD400R
SSDCRT400
SSDRTS451/SSDRTS451KEY
(30 to 61 cm)
(61 to 122 cm)
(1.2 to 2.4 m)
(2.4 to 3.7 m)
24 VDC (20 - 30)
24 VAC (20.6 - 26.4)
mA rms MAX.
Alarm
Standby
Standby
182
26
65
29
--
--
--
17.3
--
--
17.3
--
140
157
95
11
The currents shown for the
14506873-001 are maximum val-
mA DC MAX.
ues with no accessories.
* All accessory currents are
Alarm
additional to 14506873-001.
87
There are no additional cur-
rents for accessories in stand-
15
by.
10
**
SSDRTS451/SSDRTS451KEY
10
when the magnet is held in
103
place to initiate an alarm.
I56-475-09R