Tempco Instruction Manual
1/8 DIN Solid State Temperature Controller– Relay
Output–Solid State Output–For Heating
TEC-805
The TEC-805 is designed to fit panel cutouts that are 1.781" (45mm) x 3.625" (92mm).
3" minimum depth is required to provide clearance for rear terminal connections.
Input
Thermocouple (T/C)
RTD
Cold junction compensation
Input break protection
Input impedance
Common mode rejection (CMR)
Normal mode rejection (NMR)
Control Output
Relay—heating
Optional:
20VDC
4–20mA
Relay—alarm
Control Modes
On-Off
Proportional
Indication
Output
Set Point
Resolution
Accuracy
Repeatability
Manual Reset
Power
Rating
Consumption
Environmental and Physical
Operating Temperature
Humidity
Insulation
Breakdown
Vibration
Shock
Weight
Dimensions
Height:
Depth behind panel:
Panel cutout
DIN case
Type K, J. See Control label.
3-wire PT100 DIN or JIS
Automatic
Built-in, upscale on open sensor and output off
10M ohm
CMRR 120dB, min.
NMRR 60dB, min. (60Hz)
SPDT relay, 5 amps max resistive load at 120V, 240VAC, or 24VDC
For output to solid state relay
For output to SCR
SPST relay, 2 amps max resistive load at 120V or 240VAC
Differential 0.5% of full-scale range
Proportional Band fixed at 2.5% of range. Proportional Cycle time 20 seconds
for relay controls, 1 second for SSR controls
Red LED lit, heater on/LED not lit, heater off.
±1 Least significant digit
±1% of span
±1 significant digit
Adjustable up to 2.6% of span
90–264VAC, 50/60Hz.
24VAC/DC models can be special ordered.
Less than 3VA.
32–122°F (0–50°C)
0–90% RH (non-condensing)
20M ohm min. (500VDC)
2000VAC, 50/60Hz, 1 minute
10–55Hz, amplitude 1.0mm
660ft/s (20g)
8oz. (227g)
3.75" (96mm) x Width: 1.875" (48mm) x Depth: 3.125" (80mm)
2.559" (65mm)
1.871" x 3.625" (46mm x 92mm)
Plastic full plug-in construction with screw terminals on rear and adjustable
brackets for panel mounting.
Page 1 of 4
Revision 9/2016