Eclipse 705 Installation And Operating Manual

Guided wave radar level transmitter

Advertisement

705
software V3.x
nstallation and Operating Manual
Guided Wave Radar
Level Transmitter
®

Advertisement

Table of Contents

Troubleshooting

loading

Summary of Contents for Eclipse 705

  • Page 1 ™ software V3.x nstallation and Operating Manual Guided Wave Radar Level Transmitter ®...
  • Page 2 Because the enclosure of the Guided Wave Radar Level Transmitter Eclipse Model 705-5xxx-x1x and 705-5xxx-x7x and/or Probe Eclipse Model 7xx-xxx-xxx is made of aluminium, if it is mounted in an area where the use of category 1G apparatus is required, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
  • Page 3 Coaxial GWR probes are ideally suited for use in stillwells or cages. There is no min. clearance allowance to be taken Eclipse 7MQ/7MS has a transitioning zone (zone in which into consideration. the unit does not measure accurately) at the top. Maximum Shortening of probe length level should not be higher than 25 mm (1") up to 200 mm...
  • Page 4 7M5 (solids) probe at the bottom of the tank. length. The longer the probe, the longer the blocking dis- tance will be. Eclipse twin cable GWR probes are not over- Stillwell/cages fill proof certified and not overfill safe in use.
  • Page 5 Shortening of probe length aligned from electronics down to the bottom of the GWR probe. This allows the Eclipse 705 to measure up to the pro- Cage GWR probes can be easily shortened on site. Always cess flange without any dead zone at the top of the GWR re-install the bottom spacer and adapt the new probe length probe.
  • Page 6 MOUNTING Single rod (7MF - 7MH - 7MJ) / Single cable (7M1 - 7M2) GWR probes Size: 38 mm Size: 38 mm (1 1/2") or (1 1/2") or adjustable adjustable wrench wrench High Level shutdown and Overfill protection Stillwell/cages Special consideration is necessary in any high level shut- Max.
  • Page 7 (See page 12, Item 9) Top/Bottom GWR probes (7EK) Overfill safe and Overfill proof Eclipse 7EK GWR probes are “Overfill safe” in use and “Overfill proof” certified. 1 1/2" or 2" socket weld or 1 1/2" or 2"...
  • Page 8 MOUNTING Transmitter Remote Integral Max. rotation 270° 360° rotatable: Position for optimum wiring/viewing Size: 38 mm (1 1/2") or adjustable wrench Recommended torque 60 Nm (45 ft-lbs) Remove protection Remove protection CAUTION: be careful not to bend or dirty the gold, high frequency male connector (a) and its female connector (b).
  • Page 9 WIRING CAUTION: power must be switched OFF before wiring the unit. Positive supply to (+) terminal Negative supply to (-) terminal Current loop test point (HART only) ® – – LOOP CURRENT ® Shield wire to green grounding screw (resistance to ground must be <...
  • Page 10 CONFIGURATION NOTE: When connected to an approved barrier, the intrinsically safe electronics of the Eclipse allow to remove the covers with power switched on – even if the area is known to be hazardous 2 line – 8 characters LCD Default display cycles every 5 s through Status «STATUS»...
  • Page 11: Before Starting

    34 and continuing. Probe length = cm or inches, record the exact probe length as 4 mA Level printed on the nameplate: 705-xxxx-xxx / 7Mx-xxx-xxx (0%-point) Select the dielectric scale of the media to measure: 1.4– Dielectric Offset 1.7 or 1.7–3 or 3–10 or 10–100.
  • Page 12 MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level only Screen Action Comment Transmitter Display Transmitter default values cycle every 5 seconds. Status «Status», *Status* *Level* Level «Level», % Output «% Output», and Loop «Loop». *%Output* *Loop* Transmitter Display Transmitter displays level value in selected engineering units.
  • Page 13 MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level only Screen Action Comment Enter distance in Allows to ignore level measurements near the top of the probe, BlockDis xx.x selected level units caused by e.g. condensation, crystalization. Make sure that the liquid level does NOT enter this zone.
  • Page 14 MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level & Volume Screen Action Comment Transmitter Display Transmitter default values cycle every 5 seconds. Status «Status», *Status* *Volume* Volume «Volume», % Output «% Output», and Loop «Loop». *%Output* *Loop* Transmitter Display Transmitter displays Volume Value in selected engineering units.
  • Page 15 MENU: STEP BY STEP PROCEDURE – Eclipse 705: Level & Volume Screen Action Comment Enter distance in Allows to ignore level measurements near the top of the probe, BlockDis selected level units caused by e.g. condensation, crystalization. Make sure that the liquid level does NOT enter this zone.
  • Page 16 MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface Screen Action Comment Transmitter Display Transmitter default values cycle every 5 seconds. Status «Status», *Status* *IfcLevel* Interface level «Ifclevel», % Output «% Output», and Loop *%Output* «Loop». *Loop* Transmitter Display Transmitter displays interface level in selected engineering units.
  • Page 17 MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface Screen Action Comment Enter distance in Allows to ignore level measurements near the top of the probe, BlockDis selected level units caused by e.g. condensation, crystalization. Make sure that the liquid level does NOT enter this zone.
  • Page 18 MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface & Volume Screen Action Comment Transmitter Display Transmitter default values cycle every 5 seconds. Status «Status», *Status* *IfcVol* Interface volume «IfcVolume», % Output «% Output», and Loop *%Output* «Loop». *Loop* Transmitter Display...
  • Page 19 MENU: STEP BY STEP PROCEDURE – Eclipse 705: Interface & Volume Screen Action Comment Enter distance in Allows to ignore level measurements near the top of the probe, BlockDis selected level units caused by e.g. condensation, crystalization. Make sure that the liquid level does NOT enter this zone.
  • Page 20 MENU: STEP BY STEP PROCEDURE: ADVANCED CONFIGURATION Hidden diagnostic screens. Do not acces without assistance or having followed advanced training. Screen Action Comment DispFact Review factory parameters Select «YES» to reveal Factory parameters; «NO» to hide. Select Review Diagnostic messages. A cumulative review of all diagnostic messages.
  • Page 21: Quick Start

    PACTw re™ – Configuration and Troubleshooting For more details about the use of PACTw re™ and FDT technology, refer to instruction manual 59-601 WHAT IS FDT, PACTware AND DTM QUICK START 1. Start a project • FDT (Field Device Tool) is a new interface code that describes the standardization between frame programs Open Pactware and add the Hart modem key and then (e.g, PACTw re) and DTMs (Device Type Manager).
  • Page 22 PACTw re™ – Configuration and Troubleshooting Echo Curve patterns Below screens are examples of the most typical echo curves that occur in normal operation / error condition. Normal oil/water interface Level with Blocking Distance correction Normal signal pulses from oil over water Signal pulse from level.
  • Page 23: Configuration Using Hart

    Before starting the HART configuration procedure – check if your HART commu- 250 Ω < R < 450 Ω ® ® nicator is equipped with the proper Eclipse Device Descriptors (DD’s). start up the communicator Select NO: go offline Control Room Select 4:...
  • Page 24 CONFIGURATION USING HART ® 1 Device Setup 2 Level 3 % Range 4 Loop 5 Device Variables 1 Level 2 Volume 3 IfcLvl 4 IfcVol 5 Review 1 Calibration 2 Basic Setup 3 Advanced Setup 4 Diagnostics 1 Probe Model 1 Tag 1 Trim Loop Current 1 Model...
  • Page 25: Maintenance

    PC Program The Eclipse Model 705 offers the ability to do Trending and Echo Curve analysis using a PACTware DTM. This is a powerful troubleshoot- ing tool that can aid in the resolution of some of the Error Messages shown above.
  • Page 26: Warning Messages

    MAINTENANCE WARNING MESSAGES A warning message identifies the status of the instrument. A warning message does not necessarily require immediate action but may require close attention and/or follow up. The warning message will be displayed on the unit and/or selected on the Pactware screen while the output signal will remain normal.
  • Page 27: Error Messages

    MAINTENANCE ERROR MESSAGES An error message identifies a possible instrument failure and requires an action. The error message will be displayed on the unit and/or selected on the Pactware screen while the output signal will shift to the selected error output (3.6mA, 22mA or HOLD). Display Action Comment...
  • Page 28 Recommended guidelines to select the right GWR probe: • Stratification/Interface - Relatively clean liquids: use the standard coax GWR The Eclipse transmitter is designed to measure the first probes air/media interface it detects, when configured for level - Possible build up: use the enlarged coax or twin rod measurement only.
  • Page 29 • Coating/build-up (only for 7MF/7MH/7MJ/7M1/7M2) The Eclipse 705 wih Single Rod Probe was designed to ® operate effectively in the presence of media building up. Some expected error may be generated based upon the following factors: ¨...
  • Page 30: Replacement Parts

    REPLACEMENT PARTS Hygienic Industrial CAUTION: the electronic module connects to the antenna via the “High frequency connector”. This part is extremely sensitive and brittle and requires to be handled very careful. It is recommended to exchange complete amplifier heads instead of electronic modules in the field. Partn°: Serial n°: See nameplate, always provide complete partn°...
  • Page 31 REPLACEMENT PARTS Bottom spacer - 7MF/7MJ single rod GWR probe - 7MG cage GWR probe (2"/DN50) Cable weight 7M2 Single flexible cable Cable weight for solids 7M5 dual flexible cable for solids Bottom spacer - 7MG cage GWR probe (other than 2"/DN50) Spacer 7MB Cable weight 7M1 Single flexible cable...
  • Page 32: Transmitter Specifications

    TRANSMITTER SPECIFICATIONS FUNCTIONAL/PHYSICAL Description Specification Power (at terminals) HART ® - Weatherproof / ATEX flameproof enclosure / ATEX non sparking: 11 to 36 V DC - ATEX Intrinsically Safe: 11 to 28,4 V DC Foundation Fieldbus™ / Profibus PA™: - Weatherproof / ATEX flameproof enclosure / ATEX FNICO: 9 to 32 V DC - ATEX FISCO: 9 to 17,5 V DC Output 4-20 mA with HART...
  • Page 33 TRANSMITTER SPECIFICATIONS PERFORMANCE Description Specification Reference Conditions with a 1,8 m (72") Reflection from liquid, with dielectric in center of selected range, at +20 °C (70 °F) with coaxial type GWR probe CFD threshold ¿ Linearity ¡ Coaxial/twin lead probes <...
  • Page 34: Probe Specifications

    PROBE SPECIFICATIONS Description 7MR/7MM: overfill protection coaxial probe Materials Probe 316/316L (1.4401/1.4404), Hastelloy C (2.4819) or Monel (2.4360) ® ® Process seal Teflon with Viton GFLT, Aegis PF 128 or Kalrez 4079 (consult factory for alternatives) ® ® ® Spacers Teflon ®...
  • Page 35 PROBE SPECIFICATIONS Description 7MS: saturated steam GWR probe 7MQ: saturated steam GWR probe Materials Probe 316/316L (1.4401/1.4404) Process seal High Temp PEEK with Aegis PF 128 High Temp PEEK with Aegis PF 128 Alumina Spacers High Temp PEEK Silicon nitride Probe diameter Inside rod 8 mm (0.315) –...
  • Page 36 PROBE SPECIFICATIONS Description 7MF-E/G/H & 7MH: hygienic single rod probe 316/316L (1.4401/1.4404), Hastelloy C22 (2.4602) or AL-6XN stainless steel (UNS N08367); 7MH Probe ® also available in 316L (1.4435) stainless steel Materials 7MF: PTFE (GRAS 21CFR177-1550 and USP <88> Class VI at 121 °C) Process seal 7MH: PEEK &...
  • Page 37 PROBE SPECIFICATIONS Description 7MG: cage GWR probe Materials Probe 316/316L (1.4401/1.4404), Hastelloy C (2.4819) or Monel (2.4360) ® ® Process seal Teflon with Viton GFLT, Aegis PF 128 or Kalrez 4079 (consult factory for alternatives) ® ® ® Bottom spacer 2"...
  • Page 38 PROBE SPECIFICATIONS Description 7MB: standard twin rod GWR probe Materials Probe 316/316L (1.4401/1.4404), Hastelloy C (2.4819) or Monel (2.4360) ® ® Process seal Teflon with Viton GFLT, Aegis PF 128 or Kalrez 4079 (consult factory for alternatives) ® ® ® Spacers Teflon ®...
  • Page 39 TEMPERATURE - PRESSURE RATING FOR ECLIPSE PROBE SEAL Process temperature (°C) Process temperature (°C) 7MR/7MM, 7MT/7MN, 7MG probes 7MS probes 7MJ probes 7MQ probes Process temperature (°C) Process temperature (°C) 7MD/7ML probes 7MD/7ML probes small coax enlarged coax Process temperature (°C) Process temperature (°C)
  • Page 40 TEMPERATURE - PRESSURE RATING FOR ECLIPSE PROBE SEAL Process temperature (°C) Process temperature (°C) 7MH with Viton GF 'O'-rings 7EK probes for max +260 °C 7MH with EPDM 'O'-rings 7EK probes for max +315 °C and conductive liquids only “O” RING SPECIFICATIONS ¿ – Not suited for Ammonia/Chlorine applications “O”-ring material...
  • Page 41 (3.75) (4.00) (33 or 144) 45° 2 holes 2 cable Ø 9,5 (0.37) (3.50) (4.25) entries (4.38) Integral Electronics Eclipse Housing, (45° View) Remote Electronics DIMENSIONS in mm (inches) - Twin Rod (3.28) (4.12) (3.28) (4.12) (3.28) (4.12) (4.00) (4.00) (4.00)
  • Page 42 DIMENSIONS in mm (inches) - Coaxial GWR probes (3.28) (4.12) (3.28) (4.12) (3.28) (4.12) (3.28) (4.12) (4.00) (4.00) (4.00) (4.00) (10.08) (10.08) (10.08) (10.08) 45° 45° 45° 45° 2 cable 2 cable 2 cable 2 cable entries entries entries entries "...
  • Page 43 DIMENSIONS in mm (inches) - Coaxial GWR probes Proprietary flanges Ø 229 Ø 184 (9.0) (7.25) (1.97) 45° (0.79) Ø 22 (.875) 4 (0.16) (1.125) Slots for 7MR-A, 7MD-A/V/W Venting holes (order per “x” description) for level (5.23) (.22) Fisher 249B/259B (600 lbs), carbon steel Ø...
  • Page 44 DIMENSIONS in mm (inches) - Hygienic (2.05) (2.28) (2.36) (6.89) Cable entry 43° (4.28) Integral Electronics 43° View (2.05) (2.28) (2.36) Cable entry 43° 840 or 3660 (2.75) (33 or 144) (0.75) (4.00) (3.75) 2 holes Ø 9,5 (3.50) (4.25) (0.37) Remote Electronics Process...
  • Page 45 DIMENSIONS in mm (inches) - cable GWR probe 41 (1.61) 62 (2.44) 59 (2.32) 80 (3.13) 62 (2.44) 83 (3.25) 610 (24) 610 (24) 76 (3) 76 (3) Probe Insertion Probe Insertion Probe Insertion Length Length Length Probe Insertion Probe Insertion Length Length Probe Insertion...
  • Page 46 DIMENSIONS in mm (inches) - cage GWR probe (7.37) (7.37) (7.37) Ø 71 (2.80) Ø 95 (3.77) Ø 13 (0.50) rod Ø 25 (1) rod Ø 19 (0.75) rod Probe Probe Probe Insertion Insertion Insertion Length Length Length PEEK spacer PEEK spacer Teflon spacer...
  • Page 47: Model Identification

    A complete measuring system consists of: 1. Eclipse transmitter head/electronics 2. Eclipse 705 GWR probe 3. Free of charge: Eclipse 705 DTM (PACTw re™) can be downloaded from www.magnetrol.com. interface: order code: 070-3004-002 4. Option: MACTek Viator USB HART ®...
  • Page 48 MODEL IDENTIFICATION 1. Code for ECLIPSE 705 transmitter head/electronics SEE PREVIOUS PAGE MOUNTING / HOUSING MATERIAL / APPROVAL ¿ Integral mount electronics Cast aluminium - dual compartment Weatherproof ATEX intrinsically safe (digit 5 = 1) / ATEX FISCO (digit 5 = 2 or 3) ATEX flameproof enclosure...
  • Page 49 MODEL IDENTIFICATION 2. Code for ECLIPSE 705 GWR probe BASIC MODEL NUMBER 7 M B Twin Rod GWR probe for liquid level – WHG approved ε : ≥ 1,9 7 M D HTHP GWR probe for level/interface – WHG approved ε...
  • Page 50 MODEL IDENTIFICATION 2. Code for ECLIPSE 705 GWR probe SEE PREVIOUS PAGE PROCESS CONNECTION - SIZE/TYPE EN (DIN) flanges DN 50   PN 400 EN 1092-1 Type B2 DN 25 PN 16/25/40 EN 1092-1 Type A DN 80   PN 16...
  • Page 51 MODEL IDENTIFICATION 2. Code for ECLIPSE 705 GWR probe SEE PREVIOUS PAGE INSERTION LENGTH Rigid GWR probes: specify per cm (0.39") increment 0 6 0 min 60 cm (24") 6 1 0 max 610 cm (240") – max 450 cm (177") for 7MQ / 7MS Flexible GWR probes: specify per m (3.28') increment...
  • Page 52 +315 °C (+600 °F) All liquids (ε ≥ 1,4) max +260 °C (+500 °F) complete code for ECLIPSE 705 Top/Bottom GWR probe and cage X = product with a specific customer requirement DIMENSIONS in mm (inches) A min 11/2": 64 (2.50) A min 11/2": 102 (4.03)
  • Page 53: Troubleshooting

    705 Eclipse Guided Wave Radar Transmitter ® Configuration Data Sheet Copy blank page and store calibration data for future reference and troubleshooting. Item Screen Value Value Vessel Name Vessel # Process Medium Tag # Electronics Serial # TROUBLESHOOTING Probe Serial #...
  • Page 54 705 Eclipse Guided Wave Radar Transmitter ® Configuration Data Sheet – additional Advanced Diagnostic Copy blank page and store calibration data for future reference and troubleshooting. Item Screen Value Value TROUBLESHOOTING Correct Value Incorrect Value FidTicks # of Fiducial Ticks «...
  • Page 55 Notes...
  • Page 56: Service Policy

    IMPORTANT SERVICE POLICY Owners of Magnetrol products may request the return of a control; or, any part of a control for complete rebuilding or replacement. They will be rebuilt or replaced promptly. Magnetrol International will repair or replace the control, at no cost to the purchaser, (or owner) other than transportation cost if: a.