Frequency Setting By Analog Input (Terminal 2, 4); Analog Input Selection (Pr. 73, Pr. 267) - Mitsubishi Electric FR-E720-0.1K(SC) Instruction Manual

Fr-e700 series
Table of Contents

Advertisement

Frequency setting by analog input (terminal 2, 4)

4.17 Frequency setting by analog input (terminal 2, 4)

Purpose
Selection of voltage/current input
(terminal 2, 4)
Perform forward/reverse rotation by
analog input.
Adjustment (calibration) of analog
input frequency and voltage (current)

4.17.1 Analog input selection (Pr. 73, Pr. 267)

You can select the function that switches between forward rotation and reverse rotation according to the analog input
terminal specifications and input signal.
Parameter
Name
Number
Analog input
73
selection
Terminal 4 input
267
selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 188)
(1)
Selection of analog input specifications
For the terminal 2 for analog voltage input, 0 to 5V (initial value) or 0 to 10V can be selected.
Either voltage input (0 to 5V, 0 to 10V) or current input (4 to 20mA initial value) can be selected for terminal 4 used for
analog input.
Change the input specifications to change Pr. 267 and voltage/current input switch.
Rated specifications of terminal 4 change according to the voltage/current input switch setting.
Voltage input: Input resistance 10kΩ
Current input: Input resistance 233Ω
Standard control circuit terminal model
Current input (initial setting)
Voltage input
176
Analog input selection
Bias and gain of frequency
setting voltage (current)
Initial
Setting
Value
Range
0
Terminal 2 input 0 to 10V
1
Terminal 2 input 0 to 5V
1
10
Terminal 2 input 0 to 10V
11
Terminal 2 input 0 to 5V
Standard control
circuit terminal model
0
0
1
2
±
1kΩ, maximum permissible input voltage 20VDC
±
5Ω, maximum permissible input voltage 30mA
Control circuit terminal block
Parameter that should be Set
Pr. 73, Pr. 267
Pr. 125, Pr. 126, Pr. 241,
C2 to C7 (Pr. 902 to Pr. 905)
Description
Voltage/current input switch
Safety stop function
model
Safety stop function model
Current input (initial setting)
Voltage input
Refer to Page
176
179
Without reversible
operation
With reversible
operation
Description
Terminal 4 input 4 to
20mA
Terminal 4 input 0 to 5V
Terminal 4 input 0 to
10V
Control circuit terminal block

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents