Daikin E-Series Service Manual page 336

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

SiAU18-715
Troubleshooting
Check No.06
Refer to P.329
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the air passage.
Is there any short-circuit?
NO
Check the intake air filter.
Is it very dirty?
NO
Check the dust accumulation on
the indoor unit heat exchanger.
Is it very dirty?
NO
Check No. 06
Indoor unit heat exchanger
thermistor check
Does it
conform to the
thermistor characteristic
chart?
NO
YES
YES
YES
YES
Troubleshooting for RA Indoor Unit
Provide sufficient air passage.
Clean the air filter.
Clean the heat exchanger.
Replace the indoor unit PCB.
Replace the thermistor
(replace the indoor unit PCB).
(R7131)
323

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents