Refrigerating cycle block diagram

Heat
exchanger
(Evaporator)
Refrigerating cycle temperature and pressure
Operating Condition
Standard
Cooling
Max over load
Low temp
Standard
Heating
Max over load
Low temp
32
T
1
2-way valve
Liquid side
T
2
Gas side
3-way valve
STD Pressure
(psi)
3-Way Valve
70~74
-
-
248~287
-
-
Capillary tube
Compressor
Piping Temp.[°F (°C)]
T1
T2
48~53 (9~12)
48~53 (9~12)
60~64 (16~18)
60~64 (16~18)
34~39 (1~4)
34~39 (1~4)
99~110 (37~43)
134~155 (57~68)
100~109 (38~43)
140~160 (60~71)
85~95 (29~35)
107~120 (42~49)
Heat
exchanger
(Condenser)
4-way valve
Cooling
Heating
Gas leak check point
Use Temp. Condition[°F (°C)]
Indoor
Outdoor
DB
WB
DB
80 (27)
67 (19)
95 (35)
80 (27)
67 (19)
115 (46)
67 (19)
57 (14)
67 (19)
70 (21)
60 (16)
47 (8)
70 (21)
-
75 (24)
70 (21)
60 (16)
35 (2)
WB
75 (24)
75 (24)
57 (14)
43 (6)
65 (18)
33 (1)