①Before installation
①Before installation
Install correctly according to the installation manual.
Con rm the following points:
Unit type/Power source speci cation
Accessory item
For unit hanging
For refrigerant pipe
Flat washer (M10) Paper pattern Pipe cover (large) Pipe cover (small)
Strap
8
1
1
1
4
For unit hanging
For heat insulation
For heat insulation
For xing of pipe
For unit hanging
and adjustment
of gas pipe
of liquid pipe
cover
Accessories
are inside.
②Selection of installation location for the indoor unit
① Select the suitable areas to install the unit under approval of the user.
・Areas where the indoor unit can deliver hot and cold wind suf ciently.
Suggest to the user to use a circulator if the ceiling height is over 3m to
avoid warm air being accumulated on the ceiling.
・Areas where there is enough space to install and service.
・Areas where it can be drained properly. Areas where drain pipe descend-
ing slope can be taken.
・Areas where there is no obstruction of air ow on both air return grille and air supply port.
・Areas where re alarm will not be accidentally activated by the air-conditioner.
・Areas where the supply air does not short-circuit.
・Areas where it is not in uenced by draft air.
・Areas not exposed to direct sunlight.
・Areas where dew point is lower than around 23°C and relative humidity is lower than 80%.
This indoor unit is tested under the condition of JIS (Japan Industrial Stan-
dard) high humidity condition and con rmed there is no problem. How-
ever, there is some risk of condensation drop if the air-conditioner is oper-
ated under the severer condition than mentioned above.
・Areas where TV and radio stays away more than 1m. (It could cause jamming and noise.)
・Areas where any items which will be damaged by getting wet are not placed
such as food, table wares, server, or medical equipment under the unit.
・Areas where there is no in uence by the heat which cookware generates.
・Areas where not exposed to oil mist, powder and/or steam directly such as above fryer.
② Check if the place where the air-conditioner is installed can hold the weight of the unit.
If it is not able to hold, reinforce the structure with boards and beams strong enough
to hold it. If the strength is not enough, it could cause injury due to unit falling.
③ When plural indoor units are installed nearby, keep them away for more than 4 to 5m.
Space for installation and service
4000-5000mm or more
100mm
or more
150mm or more
Obstacle
③Preparation before installation
If suspension bolt becomes longer, do reinforcement of earthquake resistant.
For grid ceiling
When suspension bolt length is over 500mm, or the gap between the ceiling
and roof is over 700mm, apply earthquake resistant brace to the bolt.
In case the unit is hanged directly from the slab and is installed on the
ceiling plane which has enough strength.
When suspension bolt length is over 1000mm, apply the earthquake resistant brace to the bolt.
Prepare four (4) sets of suspension bolt, nut and spring washer (M10) on site.
Pitch of suspension bolts and pipe position
Pitch of suspension bolts
A
24
B
24
Blowout opening
Wall
Pipes/Wires/Small parts
Accessory items
For drain pipe
For air return grille
Drain hose
Hose clamp Fixing bracket
Screw
Heay insulation
(with clamp)
1
1
1
2
1
For drain pipe
For drain hose
For xing of
For installing of
For drain hose
For xing air
connection
mounting
drain hose
xing bracket
return grille
Air return grille
5mm or more
Location of pipe outlets
Top cover
Drain line
Drain line
(rear left)
Top outlet
Right outlet
98
Rear cover
Rear outlet
Cutout parts
③Preparation before installation (continued)
Series
type
40 to 50type
Single Split (PAC)
60 to 71type
series
100 to 140type
36 to 56type
VRF (KX) series
71type
Screw
112 to 140type
Pipe position
235(Liquid piping)
135
4
Refrigerant line
75
Liquid
195(Gas piping)
piping
Unit interior
271
10 mm slope
110
Haulage
Move the box as close to the installation area as possible packed.
If it must be unpacked, wrap the unit with a nylon sling,
and be careful not to damage the unit.
Do not hold fragile plastic parts, such as the side panel,
blow louver, etc.
If you need to lay the unit on a oor after unpacking, always
put it with the intake grille facing upward.
Preparation before instalation
1. Remove the air return grille.
Slide stoppers (4 places) of the catches,
then pull out the pins ( 4 or 6 places).
3. Remove the hanging plate.
Remove the screw, and then loosen
the xing bolts.
Unscrew
8-12mm
Hanging plate
④Installation of indoor unit
Work procedure
1. Select the suspension bolt locations and the pipe hole location.
(1) Use enclosed paper pattern as a reference, and
drill the holes for the suspension bolts and pipe.
Decide the locations based on direct measurements.
(2) Once the locations are properly placed, the paper
pattern can be removed.
2. Install the suspension bolts in place.
3. Fix with 4 suspension bolts, which can endure load of 500N.
4. Check the measurements given at the right
gure for the length of the suspension bolts.
5. Fasten the hanging plate onto the suspension bolts.
<
When installed against a ceiling material,
Air supply
Fasten
at the
front
end of
an
elon-
gated
Hanging plate
hole.
6. Install the unit to the hanging plate. (See the gure at right.)
(1) Slide the unit in from front side to get it
hanged on the hanging plate with the bolts.
(2) Fasten the four xing bolts (M8: 2
each on the left and right sides) rmly.
(3) Fasten the two screws (M4: 1 each on
the left and right sides).
(left)
WARNINIG : Hang a side panel on from the
panel side to the rear side and
then fasten it securely onto
the indoor unit with screws.
To ensure smooth drain ow, install the unit with
a descending slope toward the drain outlet.
CAUTION : Do not give the reversed slope, which may cause water leaks.
116
-
-
'16 • SCM-T-199
※Pipes can be taken out in 3 directions (rear, right or
top).
(mm)
・ Cut out holes using nippers, etc.
A
B
・ Cut out holes to take out pipes along the cutoff line
1070
1022
on the rear cover.
1320
1272
・ Cut out the top face cover aligning to the piping
1620
1572
position.
1070
1022
・ When taking pipe out to right-hand side, cut out a
hole along the groove at the inside of side panel.
1320
1272
・ After installing pipes and wires, seal clearances
1620
1572
around pipes and wires with putty, etc. to shut off
dust.
Make sure to install the covers at rear and top in order to
Gas
protect the inside of unit from intrusion of dust or protect
piping
Drain piping (left)
wires from damages by sharp edges. When taking them
out to the right-hand side, remove burrs or sharp edges
from the cutout.
76
Drain piping
(right)
2. Remove the side panel.
Remove the screw and detach the
side panel by sliding it toward the
direction indicated by the arrow mark.
Filter
Side panel screw
Pin
(1 each on the left and right) (M4)
Side panel
Hanging plate
screw(M4)
Indoor
Hanging
unit
plate xing
bolts(M8)
Hanging plate
>
<
No ceiling material to install against,
Suspension bolt
Hanging plate
Unit
Unit
Ceiling surface
Washer
(accessory)
※Double nuts
※Please fasten rmly with double nuts.
Hanging plate
Fixing bolts
(M8)
(For left-side drain
connection, give the
reverse slope.)
Grille upside
(Indoor unit)
Paper pattern
Ceiling
Hanging plate
Suspension bolt
>
Suspension bolt
Nut
Washer
(accessory)
※Double nuts
Screw for
hanging
plate (M4)