• IEC 62040-4: Environmental aspects - Requirements and reporting CE mark CE compliance contact: Eaton I.F . – 110 rue Blaise Pascal – 38330 Montbonnot Saint Martin - France The EC Declaration of Conformity is available upon request for products with a CE mark.
• During the replacement of the Battery Module, it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety. In case of doubt, don’t hesitate to contact your EATON representative. Page 4...
Before installing 5SC, please read the booklet presenting the safety instructions. Then follow the indications in this manual. To discover the entire range of EATON products and the options available for the 5SC range, we invite you to visit our web site at www.eaton.com/powerquality or contact your EATON representative.
2. Presentation 2.2 Rear panels 5SC 1000i Rack2U and 5SC 1500i Rack2U 5SC 2200i RT2U 5SC 3000i RT2U (1) Socket for connection to AC power source (2) Slot for optional communication card (3) Outlets for connection of equipment (4) RS232 communication port...
2. Presentation 2.3 Control panel The UPS has a three-button LCD. It provides useful information about the UPS itself, load status, events, measurements and settings. ON/OFF button Scroll down Mute alarm 2.4 LCD description UPS ON AVR mode Battery mode Internal fault Output load level Battery level...
3. Installation 3.1 Unpacking and contents check (19) 5SC UPS (20) Rail and wall mounting kits (21) Quick start, safety instructions and environmental document (22) RS232 communication cable (23) USB communication cable (24) 2 connection cables for the protected equipment (25) Cable locking systems (26) 2 supports for tower position (5SC 2200i RT2U and 3000i RT2U models only)
Only for 5SC 2200i RT2U and 5SC 3000i RT2U models 3.3 Installation of rack models 5SC 1000i Rack2U and 5SC 1500i Rack2U models Follow steps 28 to 30 for model mounting on the rails. Use provided screws on step 28 of installation. Using a longer screw could present a safety risk.
Page 12
Follow steps 31 to 33 for model mounting on the rails. Use provided screws on step 33 of installation. Using a longer screw could present a safety risk. The rails and necessary hardware are supplied by EATON Page 12 5SC 1 - 3 KVA US_EN...
3. Installation 3.4 Wall mounting of rack models Only for 5SC 1000i Rack2U and 5SC 1500i Rack2U Use provided screws on step 35 of installation. Using a longer screw could present a safety risk. Page 13 5SC 1 - 3 KVA US_EN...
(22) to the USB (5) or RJ45 (4) communication port on the UPS. The UPS can now communicate with EATON power management software. Installation of the communication cards (optional) It is not necessary to shut down the UPS before installing a communication card.
3. Installation 3.6 UPS remote control functions The 5SC offers a choice between two remote control functions. • RPO: Remote Power Off allow a remote contact to be used to disconnect all the equipment connected to the UPS. Restarting the UPS requires manual intervention. • ROO: Remote ON/OFF allows remote action of button to shut down the UPS.
4. Operation 4.1 Start-up and Normal operation To start the UPS: 1. Verify that the UPS power cord is plugged in. 2. Press the button on the UPS front panel for at least 2 seconds. 3. Check the UPS front panel display for active alarms. If the indicator is on, do not proceed until all alarms are cleared.
5. Maintenance 5.1 Troubleshooting Operation status Possible cause Action Overload Power requirement exceeds the Remove some of the equipment UPS capacity (greater than 105 % from the UPS. The UPS continues of nominal). to operate, but may shutdown if the load increases. The alarm resets when the condition becomes inactive.
Mounting the new battery module Carry out the above instructions in reverse order. • To ensure safety and high performance, use only batteries supplied by EATON. • Take care to firmly press together the two parts of the connector during remounting.
6. Appendices 6.1 Technical specifications Transformer Filter "AVR" Charger Inverter Battery 5SC 1000i 5SC 1500i 5SC 2200i 5SC 3000i Rack2U Rack2U RT2U RT2U 1000 VA 1500 VA 2200 VA 3000 VA Output Power @ 230 V 700 W 1050 W 1980 W 2700 W AC Input power...
6. Appendices 6.2 Glossary Time during which the load can be supplied by the UPS operating on battery power. Backup time Battery test Internal UPS test to check battery status. Cold start The devices connected to the UPS can be started even if AC input power is not available.