Table 3.2 Recommended Cable Size And Torque Requirements; Table 3.3 Crimp Type Compression Lug - Mitsubishi 7011A SERIES Owner Technical Manual

Single phase product 6kva, 8kva, 10kva, 12kva
Table of Contents

Advertisement

MITSUBISHI
ELECTRIC

TABLE 3.2 Recommended Cable Size and Torque Requirements

UPS Capacity
(kVA)
6kVA
(208V)
8kVA
(208V)
10kVA
(208V)
12kVA
(208V)
*1 - Voltage drop across power cables not to exceed 3% of nominal source voltage.
*2 - Allowable ampere ratings based on 90
No more than 3 conductors in a raceway without de-rating. Use copper conductors rated 90

TABLE 3.3 Crimp Type Compression Lug

Wire
Wire
Size
Strand
(Code)
Class
10
8
6
NOTE: When using crimp type lugs, the lugs should be crimped to the
FIGURE 3.2 UPS Terminal Designation
AC input
Terminals:
CB1
INPUT
L1, N, L2
B+
B-
G
7011A SERIES UPS
OWNERS / TECHNICAL MANUAL
Input Side *1
Cable Size
Torque (in. lbs)
2
10 AWG *
or larger
2
8 AWG *
or larger
2
6 AWG *
or larger
2
6 AWG *
or larger
°
C insulation at an ambient temperature of 40
Recommendation
Vendor
B
BURNDY
B
BURNDY
B
BURNDY
specifications given in the manufacturer's instructions for both
crimp tool and lug.
CONVERTER
FO
FB
CB2
BATTERY
MITSUBISHI ELECTRIC 7011A SERIES UPS
Cable Size
80
10 AWG *
in. lbs
or larger
80
8 AWG *
in. lbs
or larger
80
6 AWG *
in. lbs
or larger
80
6 AWG *
in. lbs
or larger
Crimp tool required
BUNRNDY type Y35 or Y46
Cat. No.
Color key
YAV10 T3BOX
YA8C-L1 BOX
YA6C-L BOX
BLUE
Static Transfer
Switch
INVERTER
FI
Page Number:
3-4
Output Side *1
Torque (in. lbs)
2
80
in. lbs
2
80
in. lbs
2
80
in. lbs
2
80
in. lbs
°
C.
Die index
-
-
RED
49
7 / 374
Output
Terminals:
52CS
OUTPUT
L1, N, L2
UPS Module
°
C.