TABLE 3.2 Recommended Cable Size and Torque Requirements
UPS Capacity
(kVA)
6kVA
(208V)
8kVA
(208V)
10kVA
(208V)
12kVA
(208V)
*1 - Voltage drop across power cables not to exceed 3% of nominal source voltage.
*2 - Allowable ampere ratings based on 90
No more than 3 conductors in a raceway without de-rating. Use copper conductors rated 90
TABLE 3.3 Crimp Type Compression Lug
Wire
Wire
Size
Strand
(Code)
Class
10
8
6
NOTE: When using crimp type lugs, the lugs should be crimped to the
FIGURE 3.2 UPS Terminal Designation
AC input
Terminals:
CB1
INPUT
L1, N, L2
B+
B-
G
7011A SERIES UPS
OWNERS / TECHNICAL MANUAL
Input Side *1
Cable Size
Torque (in. lbs)
2
10 AWG *
or larger
2
8 AWG *
or larger
2
6 AWG *
or larger
2
6 AWG *
or larger
°
C insulation at an ambient temperature of 40
Recommendation
Vendor
B
BURNDY
B
BURNDY
B
BURNDY
specifications given in the manufacturer's instructions for both
crimp tool and lug.
CONVERTER
FO
FB
CB2
BATTERY
MITSUBISHI ELECTRIC 7011A SERIES UPS
Cable Size
80
10 AWG *
in. lbs
or larger
80
8 AWG *
in. lbs
or larger
80
6 AWG *
in. lbs
or larger
80
6 AWG *
in. lbs
or larger
Crimp tool required
BUNRNDY type Y35 or Y46
Cat. No.
Color key
YAV10 T3BOX
YA8C-L1 BOX
YA6C-L BOX
BLUE
Static Transfer
Switch
INVERTER
FI
Page Number:
3-4
Output Side *1
Torque (in. lbs)
2
80
in. lbs
2
80
in. lbs
2
80
in. lbs
2
80
in. lbs
°
C.
Die index
-
-
RED
49
7 / 374
Output
Terminals:
52CS
OUTPUT
L1, N, L2
UPS Module
°
C.