Measures Of Other Outdoor Unit Error - Samsung AG042KSVANH Service Manual

System air conditioner dvm chiller
Hide thumbs Also See for AG042KSVANH:
Table of Contents

Advertisement

4-3-20. Measures of other outdoor unit error

Inverter / Hydro control part display
Judgment Method
Cause of problem
1. Judgement by code
Code
E347
FAN2 wire unconnected error
E447
FAN1 wire unconnected error
E367
COMP.2 wire unconnected error
E467
COMP.1 wire unconnected error
E399
FAN2 PBA IPM temperature sensor error
E499
FAN1 PBA IPM temperature sensor error
E374
Inverter PBA2 IGBT temperature sensor error
E474
Inverter PBA1 IGBT temperature sensor error
FAN2 wire unconnected
error
FAN1 wire unconnected
error
COMP.2 wire unconnected
error
COMP.1 wire unconnected
error
∙ Refer to the measures code below.
∙ Refer to the measures code below.
Error
Measures
1. Check the FAN motor and PBA connection.
2. When connected Inverterr checker, if LED operates in the
normality : External factors or when LED operates by abnor-
mality, replace the FAN PBA.
1. Check the FAN motor and PBA connection.
2. When connected Inverterr checker, if LED operates in the
normality : External factors or when LED operates by abnor-
mality, replace the FAN PBA.
1. Check the Compressor and Inverter PBA connection.
2. When connected inverter checker, if LED operates in the
normality : External factors or when LED operates by abnor-
mality, replace the Inverter PBA.
1. Check the Compressor and Inverter PBA connection.
2. When connected inverter checker, if LED operates in the
normality : External factors or when LED operates by abnor-
mality, replace the Inverter PBA.
Replace FAN PBA
Replace FAN PBA
Replace Inverter PBA
Replace Inverter PBA
60
FAN2 PBA IPM temperature
sensor error
FAN1 PBA IPM temperature
sensor error
Inverter PBA2 IGBT tempera-
ture sensor error
Inverter PBA1 IGBT tempera-
ture sensor error

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents