CORRECTION FACTORS

9-2. HYPER HEATING INVERTER

9-2-1. COOLING CAPACITY CORRECTION FACTORS
Outdoor unit
5m (16ft)
PUZ-HA30NHA5
PUZ-HA36NHA5
1.00
PUZ-HA42NKA
9-2-2. HEATING CAPACITY CORRECTION FACTORS
Outdoor unit
5m (16ft)
PUZ-HA30NHA5
1.00
PUZ-HA36NHA5
PUZ-HA42NKA
9-2-3. CAPACITY CORRECTION
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
Corrected pipe length (ft) = actual pipe length (ft) + number of bends x 1 (ft)
100
95
90
85
80
75
Note: The permitted pipe length is up to 75m<245ft>.
70
5
10
<16>
<33>
<50>
When HAs pipe is one size larger than standard size, capacity can be obtained by referring to capacity curves of
standard size.
9-2-4. ADDITION OF REFRIGERANT
• Additional charging is not necessary if the pipe length does not exceed 30 m (100 ft).
• If the pipe length exceeds the specified length above, charge the unit with additional R410A refrigerant according to the
permitted pipe lengths in the chart below.
* When the unit is stopped, charge the unit with the additional refrigerant through the liquid stop valve after the pipe
extensions and indoor unit have been vacuumized.
* When the unit is operating, add refrigerant to the gas check valve using a safety charger. Do not add liquid refrigerant
directly to the check valve.
* After charging the unit with refrigerant, note the added refrigerant amount on the service label (attached to the unit).
• Be careful when installing multiple units. Connecting to an incorrect indoor unit can lead to abnormally high pressure and have
a serious effect on operation perform ance.
Max. pipe
Max. height
Model
length
difference
HA30,
75 m
30 m
HA36,
245 ft
100 ft
HA42
Due to continuing improvement, above specification may be subject to change without notice.
86
10m (33ft)
20m (70ft)
30m (100ft) 40m (130ft) 50m (165ft) 55m (180ft) 60m (195ft) 70m (230ft) 75m (245ft)
0.985
0.957
0.931
10m (33ft)
20m (70ft)
30m (100ft) 40m (130ft) 50m (165ft) 55m (180ft) 60m (195ft) 70m (230ft) 75m (245ft)
0.997
0.991
0.985
15
20
25
30
35
40
<70>
<80>
<100>
<115>
<130>
Corrected pipe length [m]
30 m
33 m
37 m
40 m
43 m
100 ft
110 ft
120 ft
130 ft
140 ft
0 oz
6 oz
12 oz
18 oz
24 oz
0 kg
0.2 kg 0.4 kg 0.5 kg 0.7 kg 0.9 kg 1.0 kg 1.2 kg 1.4 kg 1.5 kg 1.7 kg 1.9 kg 2.0 kg 2.2 kg 2.3 kg 2.4 kg
P-Series (March 2017)
Refrigerant piping length (one way)
0.908
0.886
Refrigerant piping length (one way)
0.979
0.973
45
50
55
60
65
<150>
<165>
<180>
<195>
<215>
Additional refrigerant charging amount
46 m
49 m
52 m
55 m
150 ft
160 ft
170 ft
180 ft
30 oz
36 oz
42 oz
48 oz
0.876
0.865
0.846
0.970
0.967
0.961
Heating HA30,36,42 models
Cooling HA30,36,42 models
Cooling
Heating
70
75
m
<230>
<245>
<ft>
58 m
61 m
64 m
67 m
190 ft
200 ft
210 ft
220 ft
54 oz
60 oz
66 oz
72 oz
© 2017 Mitsubishi Electric US, Inc.
0.838
0.958
70 m
73 m
75 m
230 ft
240 ft
245 ft
78 oz
84 oz
86 oz