Messages - Siemens S7-1200 TELECONTROL Operating Instructions Manual

Hide thumbs Also See for S7-1200 TELECONTROL:
Table of Contents

Advertisement

Partner number (inter-station communication)
Specify the partner CP for inter-station communication for the selected data point by
selecting the partner number from the drop-down list.
The partners you specified in the table of the "Partner stations" > "Partner for inter-station
communication" can be selected. The access ID of the relevant partner is shown in brackets.
Data point index
Index of the corresponding data point on the communications partner.
Note:
● The data pair of the sending and receiving CP must have an identical data point index. A
receiving data point of CP 2 corresponds to a sending data point of CP 1 with the same
data point index.
● For the opposite communications direction, a second pair of data points must be created:
A sending data point of CP 2 corresponds to the receiving data point of CP 1. Once
again, both have an identical data point index.
4.9.8

Messages

Configuring SMS messages
If important events occur, the CP can send SMS messages. The recipient can be a mobile
phone or an S7-1200.
You configure the SMS message in STEP 7 in the data point and message configuration.
You can find this using the project tree:
Project > Directory of the station > Local modules > CP
For the view in STEP 7, refer to the section Configuring data points and messages
(Page 61).
You will find the character set supported for the text of the SMS message in the section
Programming SMS messages via OUC (Page 95).
For the configuration of the SMSC, refer to the section Mobile wireless communications
settings (Page 49).
Configuring e-mails
If important events occur, the CP can send e-mails. The recipient can be a PC with an
Internet connection or an S7-1200.
You configure the e-mails in STEP 7 in the data point and message configuration. You can
find this using the project tree:
Project > directory of the relevant station > Local modules > CP
For the view in STEP 7, refer to the section Configuring data points and messages
(Page 61).
CP 1242-7 GPRS V2
Operating Instructions, 10/2016, C79000-G8976-C311-02
Configuration and operation
4.9 STEP 7 configuration
83

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-1200 - telecontrolCp 1242-7 gprs v2

Table of Contents