Parameters/address space
5.6 Parameters of the analog on-board I/O
Configurable parameters and default settings for outputs
Table 5- 8
Configurable "Diagnostics" parameters
Parameters
Diagnostics
Wire break
•
2)
Short-circuit to ground
•
Overflow
•
Underflow
•
All parameters can be set channel-selective
1)
Only for the "Current" output type
2)
Only for the "Voltage" output type
3)
Table 5- 9
Configurable output parameters
Parameters
Output parameters
Output type
•
Output range
•
Reaction to CPU STOP
•
Substitute value
•
All parameters can be set channel-selective
1)
Short-circuit detection
The diagnostics for short circuit to ground can be configured for the voltage output type.
Short-circuit detection is not possible for low output values. The output voltages must
therefore be under -0.1 V or over +0.1 V.
Wire break detection
The diagnostics for wire break can be configured for the current output type. Wire break
detection is not possible for low output values; the output currents must therefore be below -
0.2 mA or above +0.2 mA.
112
1)
Yes/No
Yes/No
3)
Yes/No
Yes/No
1)
See section Output type and
output ranges of the analog
on-board I/O (Page 110)
Turn off
•
Keep last value
•
Output substitute value
•
Must be within the permitted
voltage/current output range.
See "Valid substitute value for
the output range" table in the
section Structure of a data
record for output channels of
the analog on-board I/O
(Page 155)
Value range
No
No
No
No
Value range
Voltage
±10 V
Turn off
0
Default
Reconfiguration in RUN
Yes
Yes
Yes
Yes
Default
Reconfiguration in RUN
Yes
Yes
Yes
Yes
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB