Outdoor Unit Failure Mode Table - Mitsubishi Electric MXZ-2D33VA-E1 Service Manual

Outdoor unit
Hide thumbs Also See for MXZ-2D33VA-E1:
Table of Contents

Advertisement

3. Outdoor unit failure mode table

MXZ-2D
Upper or
left lamp of
OPERATION
Abnormal point
INDICATOR
(Failure mode/protection)
lamp (Indoor
unit)
OFF
None (Normal)
2-time fl ash
Outdoor power system
3-time fl ash
Discharge temperature
thermistor
Defrost thermistor
Ambient temperature
thermistor
Fin temperature thermistor
P.C. board temperature
thermistor
Outdoor heat exchanger
temperature thermistor
4-time fl ash
Overcurrent
Compressor
5-time fl ash
Discharge temperature
6-time fl ash
High pressure
7-time fl ash
Fin temperature
P.C. board temperature
8-time fl ash
Outdoor fan motor
9-time fl ash
Nonvolatile memory data
Power module
10-time fl ash
Discharge temperature
11-time fl ash
Current sensor
Bus-bar voltage
14-time fl ash
Stop valve
17 time fl ash
Outdoor refrigerant system
abnormality
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-4).
OBH626H
LED indication
(Outdoor P.C. board)
LED 1
LED 2
Not lighted Not lighted —
Lighted
Lighted
Overcurrent protection cut-out operates
3 consecutive times within 1 minute after
the compressor gets started.
Compressor protection cut-out
operates 24 consecutive times within
10 seconds after the compressor gets
started.
Lighted
Once
Thermistor shorts or opens during
compressor running.
Lighted
Once
Lighted
Twice
Lighted
3 times
Lighted
4 times
Lighted
9 times
Once
Not
The overcurrent fl ows into intelligent
lighted
power module.
Twice
Not
The overcurrent fl ows into intelligent
lighted
power module within 10 seconds after
the compressor gets started.
( The compressor gets restarted in
15 seconds.)
9 times
Not
Waveform of compressor current is dis-
lighted
torted.
Lighted
Lighted
Discharge temperature exceeds 116 ºC
during operation.
Lighted
Lighted
The outdoor heat exchanger temperature
exceeds 70 ºC during cooling or the in-
door gas pipe temperature exceeds
70 ºC during heating.
3 times
Not
The fi n temperature exceeds 90 ºC
lighted
during operation.
4 times
Not
The P.C. board temperature exceeds
lighted
80 ºC during operation.
Lighted
Lighted
Failure occurs 3 consecutive times
within 30 seconds after the fan gets
started.
Lighted
5 times
Nonvolatile memory data cannot be read
properly.
7 times
Not
The output of the power module that
lighted
drove the compressor was shorted or
the winding of the compressor was
shorted.
Lighted
Lighted
The discharge temperature is kept
under 50 ºC (COOL mode)/40 ºC (HEAT
mode) for more than 40 minutes.
8 times
Not
The sensor circuit of current of
lighted
compressor shorts or opens during
compressor operate.
6 times
Not
The bus-bar voltage exceeds 430 V or
lighted
falls to 50 V or below during compres-
sor operating.
Lighted
12 times The current of compressor is power
module is out of order.
Lighted
17 times A closed valve and air trapped in the re-
frigerant circuit are detected based on the
temperature sensed by the indoor and
outdoor thermistors and the current of the
compressor.
124
Condition
• Check the compressor connecting
wire.
• Refer to 11-6.
inverter/compressor".
• Check the stop valve.
• Refer to 11-6.
door thermistors".
• Replace the inverter P.C. board.
• Refer to 11-6.
door thermistors".
• Check the compressor connecting
wire.
• Refer to 11-6.
inverter/compressor".
• Check the stop valve.
• Check the compressor connecting
wire.
• Refer to 11-6.
inverter/compressor".
• Check the refrigerant circuit and
the refrigerant amount.
• Refer to 11-6.
• Check the refrigerant circuit and
the refrigerant amount.
• Check the stop valve.
• Check the around outdoor unit.
• Check the outdoor unit air pas-
sage.
• Refer to 11-6.
door fan motor".
• Refer to 11-6.
door fan motor".
• Replace the inverter P.C. board.
• Refer to 11-6.
inverter/compressor".
• Check the refrigerant circuit and
the refrigerant amount.
• Refer to 11-6.
• Replace the inverter P.C. board.
• Check the power supply.
• Replace the inverter P.C. board.
• Check the stop valve.
• Check the refrigerant circuit and
the refrigerant amount.
• Check for a gas leak in a connecting
piping etc.
• Check the stop valve.
• Refer to 11-6.
door refrigerant circuit".
Indoor/
outdoor
unit failure
Remedy
mode
recall
function
"How to check
"Check of out-
"Check of out-
"How to check
"How to check
"Check of LEV".
"Check of out-
"Check of out-
"How to check
"Check of LEV".
"Check of out-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents