How To Remove The Electrical Parts - Mitsubishi Electric EHST20C-VM6HB Service Manual

Cylinder unit
Hide thumbs Also See for EHST20C-VM6HB:
Table of Contents

Advertisement

DISASSEMBLY PROCEDURE

3. How to remove the electrical parts

(Steps (1) through (3) are applied to all the following parts.)
<Control box cover> (Photo 3-1)
(1) Remove the front panel. (Refer to Procedure 1).
(2) Remove the 4 screws holding the control box cover.
(3) Slightly lift and pull out the control box cover.
<Earth leakage circuit breaker> (Photo 3-2)
(4) Disconnect all the lead wires from the earth leakage cir-
cuit breaker.
(5) Remove the 2 screws on the earth leakage circuit breaker.
Note:
To avoid dropping of the breaker, hold the breaker by
hand when removing the last screws.
<Contactor> (Photo 3-2)
(4) Disconnect all the lead wires from the contactors.
(5) Remove the 2 screws on each contactor.
Note:
To avoid dropping of the contactors, hold the contac-
tors by hand when removing the last screws.
To prevent an electrical shock, wait until all the LED
lamps on the FTC4 control board are turned off.
<Terminal block> (Photo 3-2)
(4) Disconnect all the lead wires from the terminal block. (To
disconnect the S1, S2 and S3 lead wires, disengage the
locks by pressing on the claws.)
(5) Remove the screw on the terminal block.
Note: To avoid dropping of the terminal block, hold the
terminal block by hand when removing the screw .
<Controller board> (Photo 3-3)
(4) Disconnect all the lead wires from the controller board.
(5) Remove the controller board from the 6 board supports.
OCH531
PHOTOS
Control box cover
Photo 3-1
fixing screws
Control box
cover
Control box cover
fixing screws
Photo 3-2
Control box
Controller
board
Terminal block (TB1)
w The photos shown are of the EHST20C-YM9HB model.
Photo 3-3
70
Earth leakage circuit
breakers (ECB1, ECB)
Contactors
Controller
board

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents