Operating Guide
MENU > Alarm > Charge T
MENU > Alarm > Temp. monitor
Lowest temp.
Circuit
All
The alarm function will not be activated if the desired flow / duct
temperature is lower than the set value.
* See Appendix "Parameter ID overview"
MENU > Alarm > Supply T
MENU > Event > Supply T
Delay
Circuit
All
The alarm is activated if the supply temperature S2 does not get higher than
('Desired buffer temperature' + 'Pump start diff. ' ).
Example: 60 °C + 3 K = 63 °C
* See Appendix "Parameter ID overview"
MENU > Alarm > Alarm overview
Alarm overview, in general
Circuit
All
Access to overview showing the alarm number / alarm type. The alarm
number is entered into the alarm register and can be obtained from a
SCADA system.
Example: "5: Temp. monitor": If an alarm is activated because of conditions
in 'Temp. monitor' the alarm number 5 is placed in the alarm register.
Danfoss District Energy
ECL Comfort 310, application A319
1x150
Setting range
Factory setting
*
1x340
Setting range
Factory setting
*
Setting range
Factory setting
If the cause of the alarm disappears, the alarm indication and output
also disappear.
*
*
VI.JM.L2.02
DEN-SMT/DK
75